Heating Troubleshooting; Variable Frequency Drive (Vfd) Troubleshooting; Phase Loss Protection - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Heating
Troubleshooting
Use
the unit
Scrolling
Marquee
display
or a CCN
device
to view
the heating
status
display
and
the
heating
diagnostic
display
(see
Appendix
A)
for information
on the heating
operation.
Check
the
current
alarms
and
alarm
history
for
any
heating
alarm
codes
and
correct
any
causes.
(See
Table
12.)
Verify
any
unique
control
configurations
per
installed
site
requirements
or
accessories.
If
alarms
conditions
are corrected
and cleared,
operation
of the heat
stages
and
indoor
fan
may
be
verified
by
using
the Service
Test
mode.
(See
Table
5.)
Gas Heat (48PD Units Only)
See
Table
12 for general
gas heating
service
analysis.
See
Fig. 9 for
service
analysis
of the IGC
board
logic.
Check
the status
LED
on
the IGC board
for any
flashing
alarm
codes
and correct
any causes.
(See
Table
13.)
Electric Heat (50PD Units Only)
See
Table
14 for electric
heating
service
analysis.
Variable
Frequency
Drive (VFD) Troubleshooting
The VFD must be in "Auto" mode and when commanding it to
100% the voltage signal should be 10vdc across AI1 and AIGND.
Verify all parameters are correct to factory defaults. See Appendix
B for parameters and additional troubleshooting.
Phase Loss Protection
The phase loss protection
option will monitor the three-phase
electrical
system
to provide
phase
reversal
and
phase
loss
protection.
Phase Reversal
Protection
If the control senses an incorrect phase relationship, the relay (KI)
will be de-energized (opening its contact). If the phase relationship
is correct, the relay will be energized. The control has a self-bypass
flmction after a pre-set time. If the control determines that the three
phases stay in a correct relationship for 10 consecutive minutes, the
relay will stay energized regardless of the phase sequence of three
inputs as long as 24-vac control voltage is applied. This self-bypass
flmction will be reset if all three phases are restored in a phase loss
event.
Phase Loss Protection
If the reverse rotation board senses any one of the three phase
inputs has no AC voltage, the relay will be de-energized
(opening
its contact). This protection is always active as long as 24-vac
control voltage is applied, and is not affected by the self by-pass
flmction of the phase sequence monitoring flmction. However, in
the event of phase loss, the relay will be re-energized only if all
three phases are restored and the three phases are in the correct
sequence.
A red LED is provided to indicate the flmction of the board. See
the table below.
LED STATUS
FUNCTION
On Continuously
Relay contact
closed
(normal
operation).
Relay contact
open (phase
loss or phase
Blinking
reversal
has occurred)
- No power will be
supplied
to the control
system.
Off
24 vac control
power
not present
(off).
Table 12 -- Gas Heating
Service
Analysis
PROBLEM
CAUSE
REMEDY
Burners
Will
Not Ignite,
Unit is not configured
for heat.
Check heating
configurations
using
ComfortLink
_' Scrolling
Marquee.
Active alarm.
Check active alarms
using ComfortLink_'
Scrolling
Marquee
and
the IGC alert flash codes.
No power to unit.
Check power
supply, fuses, wiring,
and circuit
breakers.
No power to IGC.
Check fuses and plugs.
Heaters
off due to time guard to prevent
short
Check active alarms using ComfortLink_'
Scrolling
Marquee
and
cycling,
the IGC alert flash codes.
Occupancy
schedule
set point not calling
for
Check using ComfortLink
_' Scrolling
Marquee.
Heating.
No gas at main burners.
Water in gas line.
Inadequate
Heating,
Dirty air filters.
Gas input too low.
Occupancy
schedule
set point set too low.
Unit undersized
for load.
Restricted
or low airflow.
Too much
outdoor
air.
Limit switch
cycles
main burners.
Poor Flame
Characteristics,
Incomplete
combustion
(lack of combustion
air)
results
in: Aldehyde
odors,
CO, sooting
flame, or
floating
flame.
Burners
Will
Not Turn Off,
Unit is in Minimum
on-time.
Unit running
in Service Test mode.
Main gas valve stuck.
LEGEND
IGC
Integrated
Gas Controller
SAT
Supply Air Temperature
Check gas line for air and purge as necessary.
After purging
gas
line of air, allow gas to dissipate
for at least 5 minutes
before
attempting
to re-light
unit.
Drain water
and install drip.
Replace
air filters.
Check gas pressure
at manifold.
Refer to gas valve adjustment
in
the Service section.
Check setpoints
and adjust if necessary.
Decrease
load or increase
of size of unit.
Remove
restriction,
verify proper
fan speed
operation,
and check
SAT compared
to the SAT heating
limits.
Check economizer
position
and configuration.
Adjust
minimum
position
if needed
using ComfortLink
Scrolling
Marquee.
Verify
proper fan speed operation.
Check rotation
of blower
and temperature
rise of unit. Adjust
as
needed.
Check all screws
around
flue outlets
and burner
compartment.
Tighten
as necessary.
Cracked
heat exchanger,
replace.
Unit is over-fired,
reduce
input.
Adjust
gas line or manifold
pressure.
Check vent for restriction.
Clean
as necessary.
Check orifice to burner alignment.
Check using ComfortLink_'
Scrolling
Marquee
and the IGC alert
flash codes.
Check using ComfortLink
_' Scrolling
Marquee.
Turn off gas supply
and unit power. Replace gas valve.