Carrier 50PD05 Operating And Service Instructions page 18

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

variable orUnoccupied
Cool S et P oint
( Setpoints--->UCSP)
plus
the
Fan
Speed
Control
Demand
(Configuration--->COOL--->FS.CD)
configuration
variable
the
indoor
fan will
run
at 100%.
When
the
temperature
in the
conditioned
space
is between
the
Occupied
Cool
Set
Point
(Setpoints--->OCSP)
and
Occupied
Cool
Set
Point
(Setpoints--->OCSP)
plus
the
Fan
Speed
Control
Demand
(Configuration--->COOL--->FS.CD)
configuration
variable
the
indoor
fan
modulates
to satisfy
the
Occupied
Cool
Set Point
(Setpoints-,OCSP)
or
Unoccupied
Cool
Set
Point
(Setpoints-,UCSP).
When
the
temperature
in the conditioned
space
falls
to
0.5F
below
the
Occupied
Cool
Set
Point
(Setpoints-,OCSP)
or
Unoccupied
Cool
Set
Point
(Setpoints-,UCSP)
for 5 nfinutes
the controls
will run unit in
ventilation
mode.
See ventilation
mode
sequence
of operation
Tern )e ra_ure
ocsp
+ FSCD
X
C_oling
_peed
D el_
Window
- ]nit
Supply
Fan
._pe
ed
M o_utate_
to 1'_ OVe
Space Temperature a on 9,_
e_ned Curce o the O_cup ed Cool eet Polnt
(OO SP)
"I"-,,
OCSP
_
--
m ,
ocsP
- 05 F
• Time
C09143
Fig. 6 - Cooling
Speed
Demand
Window
Cooling
Supply
Air Set Point Reset
The PD unit can be configured
to allow
for reset
of the Cool
Supply
Air
Set Point
(Setpoint--,SASP).
This
is needed
for
applications
where
a
high
Cool
Supply
Air
Set
Point
(Setpoint--,SASP)
is required
or where
dramatic
load
changes
occur over short time periods.
In these situations
a high supply air
temperature
may not provide
enough
cooling
to reduce the Space
Temperature
(Temperatures--->AIR.T--->SPT)
to the Occupied
Cool
Set Point (Setpoints---,OCSP)
or the Unoccupied
Cool
Set Point
(Setpoints---,UCSP)
over a reasonable
time period.
The compressor
or econonfizer
operation
supplying
cooling
to the
conditioned
space
controls
to the Supply
Air Control
Point
(Run
Status--->COOL--->SA.CP).
The Supply
Air Control
Point
(Run
Status--->COOL--->SA.CP)
which
is a calculated
value that is equal
to the
Cool
Supply
Air
Set
Point
(Setpoint--->SASP)
plus the
calculated
amount
of reset
required
up
to the
values
set by
configuration
variables
SASP
Maxinmm
Reset
Down
(Configuration--->COOL--->SAT--->SA.MD)
and
SASP
Maximum
Reset Up (Configuration--->COOL--->SAT--->SAJ_U).
Reset
of the
Cool
Supply
Air
Set Point
(Setpoint--->SASP)
is
linfited
by the
configuration
variables
SASP
Maxinmm
Reset
Down
(Configuration--->COOL--->SAT--->SA.MD)
and
SASP
Maximum
Reset
Up
(Configuration--->COOL--->SAT--->SAJ_U).
The
SASP
Maximum
Reset
Down
(Configuration--->COOL--->SAT--->SA.MD)
configuration
variable
can be set from -20 to 0 F and will allow the Cool Supply
Air Set
Point (Setpoint--->SASP)
to be reset to as nmch
as 20 F below the
Cool
Supply
Air
Set
Point
(Setpoint--->SASP).
The
SASP
Maximum
Reset
Up
(Configuration--->COOL?SAT--->SAJ_U)
configuration
variable
can be set from 0 to 20 F and will allow the
Supply
Air Temperature
to be Reset to as nmch
as 20 F above the
Cool
Supply
Air
Set Point
(Setpoint--->SASP).
The
SASP
Maximum
Reset Down
(Configuration--->COOL--->SAT--->SAJ_D)
and
SASP
Maximum
Reset
Up
(Configuration--_COOL--_SAT--_SA_U)
configuration
variables
can be set independently
and do not need to be equal values above
and below
the Cool Supply
Air Set Point (Setpoint--,SASP).
For
example,
the
SASP
Maximum
Reset
Down
(Configuration--->COOL--->SAT--->
?SA J_D)
configuration
variable
can
be
set
to
-10
and
the
SASP
Maxinmm
Reset
Up
(Configuration--_COOL--_SAT--_SA_U)
configuration
variable
can be set to 0 giving
the range
of Cool
Supply
Air Set Point
(Setpoint--,SASP)
reset of +0 and -10 F.
In normal
operation
when
the
Space
Temperature
is within
the
speed
demand
window
the unit control
will modulate
the indoor
fan speed and supply
air temperature
along a defined
curve to bring
the Space Temperature
to Occupied
or Unoccupied
Cool Set Point.
Since this curve
is independent
of the conditioned
space
load the
control
scheme
will adapt to any load present
in the conditioned
space
by adjusting
the fan speed and supply
air temperature
and
move
the space
temperature
along
the defined
time temperature
curve
to Occupied
or Unoccupied
Cool Set Point.
When
the space
temperature
rises above
the Occupied
Cool
Set
Point
(Setpoints-,OCSP)
+
Fan
Speed
Control
Demand
(Configuration--->COOL--->FS.CD)
for over 2 nfinutes
or is outside
the speed
demand
window
and there
is some amount
of SASP
Maximum
Reset
Down
(Configuration--->COOL?SAT--->SA.MD)
configured
the indoor
fan will be locked
at 100%
and the unit
controls
will subtract
a calculated
amount
of temperature
reset to
the Cool Supply
Air Set Point (Setpoint--->SASP).
The indoor
fan
speed
will be locked
at 100%
as long
as reset is applied.
The
Supply
Air Temperature
will now
adjust to this new Supply
Air
Control
Point
(Run
Status--->COOL--->SA.CP).
The controls
will
continue
to
subtract
a calculated
amount
of temperature
reset
cunmlatively
to a value
equal
to the Supply
Air Temperature
Set
Point
(Setpoint--->SASP)
+
SASP
Maxinmm
Reset
Down
(Configuration--->COOL--->SAT--->SAJ_D).
When
the reset is no
longer
needed the control
will remove
Down
Reset until all reset is
removed
and
the
Supply
Air
Control
Point
(Run
Status--->COOL--->SA.CP)
is back
to the original
Supply
Air Set
Point (Setpoint--->SASP).
The indoor fan will then modulate
lower
than 100% to move
the Space Temperature
(Temperatures--->SPT)
along
the defined
time temperature
curve
to Cool
Supply
Air Set
Point
(Setpoint--->SASP)
or
Unoccupied
Cool
Set
Point
(Setpoints--->UCSP).
See Fig. 6 and 7.
Supply
Air Temperature
iiiiiiiiii!iiiiiiiiiiiiiiiiiiiiiii!iiiiiiiiiiiiiiiii_
b, iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
iiiiiiiiiii!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!iiii!
iii!iiiiiii iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
SAS
Fig. 7 - Cool
Supply
Air Set Point
Time
C09144
Cooling
Mode
with
Economizer
Using Space
Temperature
Sensor T55, T56,
T58
or T59
If
an
economizer
is
installed,
the
Economizer
Installed
configuration
(Configuration--_ECON--_
EC.EN)
should be set to
YES.
The econonfizer
is controlled
by the Econo
Commanded
Position
(Outputs'--,ECON--,
EC.CP)
on the Econonfizer
Control
Board.
If the indoor
fan is off or the building
is unoccupied,
the
econonfizer
position
is zero.
When the space temperature
is above the Occupied
Cool
Set Point
(Setpoints-,OCSP)
and the econonfizer
is installed,
configured
and working
correctly
the unit controls
will always
try to meet
space
cooling
demand
using the econonfizer
before
turning
on the
compressor.
The econonfizer
will provide
free cooling
when
the
following
outside
air conditions
are true.
18