Carrier 50PD05 Operating And Service Instructions page 100

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

APPENDIX
D - ADDITIONAL
START-UP
DATA
UNIT
50PD
05
06
Table 60 -- Air Quantity
Limits
(50PD
Units)
COOLING (cfm)
HEATING (cfm)
OPTIONAL ELECTRIC HEAT
1200
2000
1200
2000
1500
2500
1500
2500
Table 61 -- Air Quantity
Limits
(48PD
Units)
UNIT
COOLING
(cfm)
HEATING
(cfm)
48PD
Min
Max
Min
Max
05 (Low
Heat)
1200
2000
600
1680
05 (Med
Heat)
1200
2000
940
2810
05 (High
Heat)
1200
2000
1130
2820
08 (Low
Heat)
1500
2500
940
2810
08 (Med
Heat)
1500
2500
1130
2820
08 (High
Heat)
1500
2500
1510
2520
Table 62 -- Evaporator
Fan Motor Specifications
- 48/50PD
48/50PD
DRIVE
VOLTAGE/PHASE
05 & 06
Low & High
208/230-3ph
460-3ph
NOTES:
1. Extensive motor and electrical testing ensures that the motors can be utilized
with confidence
up to the maximum
applied bhp, watts, and amps. Using the fan
motor up to the maximum
ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected.
2. Convert bhp to watts using the following
formula:
bhp
(746)
watts
=
motor
efficiency
EFFICIENCY
MAX
BHP
MAX AMPS
0.80
2.0
6.4
0.80
2.0
3.2
3. The EPAC_ (Energy Policy Act of 1992) regulates energy requirements
for
specific types of indoor-fan
motors. Motors regulated by EPAC_ include any
general purpose, T-frame (three-digit,
143 and larger),
single-speed,
foot
mounted, polyphase, squirrel cage induction
motors of NEMA (National Electrical
Manufacturers
Association)
design A and B, manufactured
for use in the United
States. Ranging from 1 to 200 Hp, these continuous-duty
motors operate on 230
and 460 volt, 60 Hz power. If a motor does not fit into these specifications,
the
motor does not have to be replaced by an EPAC_-compliant
energy-efficient
motor.
Variable-speed
motors are exempt from EPACW compliance
requirements.
Therefore, the indoor-fan
motors for Carrier 48/50PG03-14
units are exempt from
these requirements.
Table 63 -- Fan Rpm at Motor
Pulley Settings*
- 48/50PD
UNIT
MOTOR
PULLEY
TURNS
OPEN
48/50PD
DRIVE
0
1/2
1
11/2
2
21/2
3
31/2
4
41/2
5
Low
910
878
847
815
784
753
721
690
659
627
596
05
High
1173
1139
1104
1070
1035
1001
966
932
897
863
828
08
Low
978
949
920
891
863
834
805
776
748
719
690
Hiclh
1261
1227
1194
1161
1128
1095
1062
1028
995
962
929
*Approximate
fan rpm shown, based on 1725 rpm motor.
NOTE: Factory speed setting is at 5 turns open.
Table
64 --
Accessory/FlOP
Pressure
Drop
(in. wg)
- 48/50PD
AIRFLOW
ELECTRIC
ECONOMIZER
ECONOMIZER
(CFM)
HEAT
(Vertical)
(Horizontal)
800
0.01
0.01
0.03
800
0.01
0.01
0.05
1000
0.02
0.02
0.07
1200
0.02
0.03
O. 10
1400
0.03
0.04
O. 14
1600
0.04
0.08
O. 17
1800
0.05
0.07
0.22
2000
0.07
0.09
0.28
2200
0.08
0.11
0.31
2400
0.10
0.13
0.37
2600
0.11
0.15
0.43
2800
0.13
0.18
0.49
3000
0.15
0.21
0.56
100