Cooling Modes - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

exceed Econ Min
at
Max
Fan
Speed
(Configuration--_ECON--_MP_X)
or
IAQ
Override
Position
(Configuration--,AIR.Q--,OVRdP)
to
provide
econonfizer
cooling.
IA.CF
= 3 (Control
Minimum
Position)
When IA.CF
= 3, an external
4 to 20 mA source is used to set the
minimum
position.
The 4mA signal corresponds
to 0% and the 20
mA signal corresponds
to 100%.
In this mode,
configuration
such
as
Econ
Min
at
Max
Fan
Speed
(Configuration--,ECON--,MP.MX),
Econo
Min
IAQ
Position
(Configuration--,AIR.Q--,AQ.MN)
and the econonfizer
nfininmm
position
and DCV
minimum
position
curves
in figure
3 are not
used.
If the indoor
fan is not operating,
the econonfizer
position
will be
zero.
The damper
position
may exceed
the econonfizer
minimum
position
to provide
econonfizer
cooling.
IAQ (Switch
Input)
Indoor air quality can also be measured
using a switch
input.
For
the purpose
of specifying
the type of switch input, low CO2 levels
are considered
normal.
The IAQ switch
input
is defined
by the
IAQ
Switch
Input
Config
(Configuration-,AIR.Q-,ILCF).
Enthalpy
and IAQ
are controlled
by the same
switch
input
and
therefore
cannot be used simultaneously.
II.CF = 0 (NO IAQ)
The II.CF
= 0, configuration
signifies
that there is no IAQ switch
input.
The damper will operate
at the Econ Min at Max Fan Speed
(Configuration_ECON_MP.MX)
and
corresponding
damper
position
curve
based
on indoor
fan speed
when
the
space
is
occupied
and the indoor
fan is on.
II.CF
= 1 (DCV Normally
Open)
II.CF
= 2 (DCV Normally
Closed)
The Demand
Control
Ventilation
(DCV)
allows
the econonfizer
minimum
position
to be decreased
when
there is no IAQ problem.
If IAQ
is low, the econonfizer
minimum
position
is Econo
Min
IAQ Position
(Configuration--_AIR.Q--_AQ_N)
when the indoor
fan
is
operating
at
Supply
Fan
Maximum
Speed
(Configuration-*UNIT-*FS.MX).
If
IAQ
is
high,
the
economizer
minimum
position
is Econ
Min at Max
Fan
Speed
(Configuration--*ECON--*MP_X)
when
the
indoor
fan
is
operating
at
Supply
Fan
Maximum
Speed
(Configuration--_
UNIT--_FS_X).
II.CF = 3 (Override
Normally
Open)
II.CF = 4 (Override
Normally
Closed)
The damper
override
function
permits
absolute
positioning
of the
economizer
damper
for ventilation
purposes.
The
override
is
active
when
IAQ
is high
and inactive
when
IAQ
is low.
The
override
position
is configured
by
the
IAQ
Override
Position
(Con figuration---,AIR.Q---,O
VR dP).
Outdoor
Air Quality
(Analog
Input)
The ComfortLink
TM control
is configured
for outdoor
air quality
sensors
which
provide
a 4 to 20 mA signal corresponding
to 0 to
2000 ppm CO2.
If a field supplied
sensor has a different
range, the
ppm display
range
nmst be reconfigured
by entering
new values
for
the
OAQ
Sensor
Value
at
4mA
(Configuration--,AIR.Q--,O.4M)
and
OAQ
Sensor
Value
at
20mA
(Configuration--,AIR.Q--,O.2OM).
OA.CF
= 0 (NO OAQ)
This signifies
that there is no outdoor
air sensor
installed.
The
default value of OAQ is 400 ppm CO2.
OA.CF
= 1 (DCV)
The outdoor
air quality
sensor analog input is the value of OAQ.
OA.CF
= 2 (OAQ
Lockout)
The outdoor
air quality
analog input
is only used to lock out the
outdoor
ventilation.
The econonfizer
commanded
position
is set to
0%
when
the
CO2
ppm
exceeds
the
OAQ
lockout
value
configured
for
the
OAQ
Lockout
Limit
(Configuration---,AIR.Q---,AQJL).
The
default
value
for OAQ
Lockout
Linfit
(Configuration---,AIR.Q---,OAQ_L)
is 600
ppm
CO2.
Fan
Enable
(Analog
IAQ
Sensor)
The
DCV
algorithm
will
operate
whenever
the
building
is
occupied
and the indoor
fan is operating
or whenever
the IAQ
algorithm
has caused the indoor
fan to operate.
The IAQ Analog
Fan
Config
(Configuration---,AIR.Q---,IA.FN)
deternfines
whether
or not the IAQ algorithm
can turn on the indoor
fan. If the
indoor
fan is not operating,
the econonfizer
position
will be zero.
The damper
position
may
exceed
Econ
Min
at Max
Fan Speed
(Configuration---,ECON---,MP_X)
and
corresponding
damper
position
curve to provide
econonfizer
cooling.
IA.FN
= 0 (Never)
When IA.FN
=0, the IAQ algorithm
can never turn on the fan.
IA.FN
= 1 (Occupied)
When
IA.FN
=1, the IAQ algorithm
will turn on the indoor
fan
whenever
the building
is occupied
and IAQ/OAQ
differential
is
greater
than
the
Fan
On
AQ
Differential
(Configuration---,AIR.Q---,DF.ON).
The indoor
fan will turn off
when
the
IAQ/OAQ
differential
is less
than
the
Fan
Off AQ
Differential
(Configuration---,AIR.Q---,DF.OF).
IA.FN
= 2 (Always)
The
indoor
fan
operation
for IA.FN
=2,
is the
same
as the
operation
when
IA.FN
=1, except
the algorithm
is not linfited
to
the occupied
periods
only.
The fan can be triggered
on when the
space is occupied
or unoccupied.
Fan
Enable
(Analog
Switch
Input)
The
DCV
algorithm
will
operate
whenever
the
building
is
occupied
and the indoor
fan is operating
or whenever
the IAQ
algorithm
has caused
the indoor
fan to operate.
The IAQ Switch
Fan Config
(Configuration---,AIR.Q---,II.FN)
deternfines
whether
or not the IAQ algorithm
can turn on the indoor
fan. If the indoor
fan is not operating,
the econonfizer
position
will be zero.
The
damper
position
may
exceed
Econ
Min
at Max
Fan
Speed
(Configuration---,ECON---,MP_X)
and
corresponding
damper
position
curve to provide
econonfizer
cooling.
II.FN
= 0 (Never)
When II.FN
=0, the IAQ algorithm
can never turn on the fan.
II.FN
= 1 (Occupied)
When
II.FN
=1, the IAQ
algorithm
will turn on the indoor
fan
whenever
the building
is occupied
and IAQ is high.
The indoor
fan will turn off when the IAQ returns
to normal.
II.FN
= 2 (Always)
The indoor
fan operation
for II.FN
=2, is the same as the operation
when
IA.FN
=1,
except
the
algorithm
is not
linfited
to the
occupied
periods
only.
The fan can be triggered
on when the space
is occupied
or unoccupied.
Cooling
Modes
Cooling
Mode
Using
Space
Temperature
Sensor
T55,
T56,
T58
or T59
In cooling
mode
the PD control
will maintain
the Occupied
Cool
Set Point
(Setpoint--_OCSP)
or the Unoccupied
Cool
Set Point
(Setpoints---,UCSP)
by modulating
the indoor
fan speed to supply
more
or less airflow
to the conditioned
space
at the Supply
Air
Temperature
(Temperatures---,AIR.T---,SAT).
Cooling
Supply
Air Set Point
The
Cool
Supply
Air
Set
Point
(Setpoint---,SASP)can
be
configured
between
45F and 75F.
The compressor
modulates
to
maintain
a
Supply
Air
Temperature
(Temperatures--+AIR.T--+SAT)at
the Cool
Supply
Air
Set Point
(S etpoint---, SA SP) .
Cooling
Speed
Demand
Window
When
the temperature
in the conditioned
space
is higher
than the
Occupied
Cool
Set Point (Setpoints---,OCSP)
plus the Fan Speed
Control
Demand
(Configuration---,COOL?FS.CD)
configuration
17