Initiate economizer
calibration
(Service
Test--,INDP--,
E.CAL)
using the Service Test menu. The economizer
calibration
procedure
will try to find new maximum
open and closed
positions.
If the alert does not clear automatically
after the
calibration
procedure
is complete,
investigate
what is limiting
economizer
rotation.
After that step, run another calibration,
but
first power off unit (spring return the damper),
loosen
the
actuator
clamp,
and while pushing
the damper
closed tighten
the
clamp. This alert resets automatically.
Economizer
Damper
Actuator
Torque Above Load Limit
This alert occurs when the actuator
load is too high.
Investigate
to determine
what is increasing
damper
load and verify that the
actuator is the correct
size for the unit.
This alert resets
automatically.
• Economizer
Damper
Actuator
Hunting
Excessively
This alert occurs when the commanded
damper
position
is
changing
too rapidly.
The stop jog ration must be less than 21%
to clear this alert. Leave the actuator
powered
with no signal for
a few hours to allow the ratio to decrease
(may have to wait
longer than a few hours).
If the alert continues,
determine
if the
ECB or actuator
is bad. This alert resets automatically.
• Economizer
Damper
Stuck or Jammed
This alarm occurs when the actuator
senses it can no longer
move. Investigate
what is stopping
the rotation
of the actuator
and fix. This alert resets automatically.
• Economizer
Damper
Actuator
Mechanical
Failure
This alert occurs when the actuator
senses a catastrophic
failure.
Investigate
actuator
and replace if necessary.
This alert resets
automatically.
• Economizer
Damper
Actuator
Direction
Switch
Wrong
Position
This alert occurs when the economizer
damper
direction
switch
is in the wrong
position.
The direction
switch should be in the
clockwise
position
and the actuator
should be mounted
so that
the CW face of the actuator
is accessible.
Correct
if necessary.
This alert clears automatically.
Alert
Code T415 - IAQ Input
Out of Range
This alert occurs when the IAQ input (on ECB) is less than 3.5 mA
and the sensor
is configured
as installed.
IAQ operation
will be
disabled.
Check sensor and wiring.
This alert clears automatically.
Alert Code T416 - OAQ Input Out of Range
This
alert occurs
when
the OAQ input
(on ECB)
is less than 3.5
mA and the sensor is configured
as installed.
OAQ operation
will
be
disabled.
Check
sensor
and
wiring.
This
alert
clears
automatically,
28