Controls Quick Start; Thermostat Control; Space Temperature Sensor Control; Space Humidity Control -- Thermidistat - Carrier 50PG20-28 Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Single package rooftop units with comfortlink tmcontrols and puron (r-410a) refrigerant
Table of Contents

Advertisement

Table 34 -- Fan Rpm At Motor Pulley Settings* -- 50PG20-28
50PG
DRIVE
Low Range Vertical
Mid-Low Range Vertical
Mid-High
Range Vertical
20 and 24
High Range Vertical
(230 and
460 volt)
Low Range
HodzontN
Mid-Low Range
HodzontN
Mid-High
Range Horizontal
High Range
Horizontal
Low Range Vertical
Mid-Low Range Vertical
Mid-High
Range Vertical
20 and 24
High Range Vertical
(575 Volt)
Low Range
HodzontN
Mid-Low Range
HodzontN
Mid-High
Range Horizontal
High Range
Horizontal
Low Range Vertical
Mid-Low Range Vertical
Mid-High
Range Vertical
28
High Range Vertical
(all voltages)
Low Range
HodzontN
Mid-Low Range
HorizontN
Mid-High
Range Horizontal
High Range
Horizontal
*Approximate
fan rpm shown
NOTE: Factory pulley speed setting
is at 3 turns open.
MOTOR
PULLEY
TURNS OPEN
O
_
1
11t2
2
21/2
3
3q 2
4
41/2
5
5tt2
6
685
706
727
749
770
791
812
833
854
876
897
918
939
949
970
992
1013
1035
1056
1078
1099
1120
1142
1163
1185
I206
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
I176
1014
I038
106I
1085
1108
1132
1156
1179
1203
1226
1250
1273
I297
685
706
727
749
770
791
812
833
854
876
897
918
939
949
970
992
1013
1035
1056
1078
1099
1120
1142
1163
1185
I206
941
961
980
1000
1019
1039
I059
I078
1098
1117
1137
1156
1176
1014
I038
106I
1085
1108
1132
1156
1179
1203
1226
1250
1273
I297
751
768
785
802
819
836
853
869
886
803
920
937
954
949
970
992
1013
1035
1056
1078
1099
1120
1142
1163
1185
I206
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
I176
1014
I038
106I
1085
1108
1132
1156
1179
1203
1226
1250
1273
I297
751
768
785
802
819
836
853
868
886
903
920
937
954
949
970
992
1013
1035
1056
1078
1099
1120
1142
1163
1185
I206
941
961
980
1000
1019
1039
I059
I078
1098
1117
1137
1156
1176
1014
I038
106I
1085
1108
1132
1156
1179
1203
1226
1250
1273
I297
687
703
718
734
749
765
780
796
811
827
842
858
873
805
822
839
856
872
889
906
923
940
857
973
980
I007
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
I176
1014
I038
106I
1085
1108
1132
1156
1179
1203
1226
1250
1273
I297
687
703
718
734
749
765
780
796
81I
827
842
858
873
805
822
839
856
872
889
906
923
940
957
973
980
I007
941
961
980
1000
1019
1039
I059
I078
1098
1117
1137
1156
1176
1014
I038
106I
1085
1108
1132
1156
1179
1203
1226
1250
1273
I297
CONTROLS
QUICK
START
The tbllowing infonnation will provide a quick guide to
setting up and confignring the 48/50PG series units with
('omfbrtLink
TM
controls. Unit controls are pre-configured at
the factory tbr factory-installed options. Field-installed acces-
sories will require configuration
at start-up. Additionally,
specific job requirements may require changes to delhult
configuration values. See the CCN and Display parameter
tables and other sections of these instructions for more details.
Thermostat
Control-
Wire accessory thermostat to
the conesponding R, Y1, Y2, Wt, W2, and G terminals on the
field connection terminal board located at the unit control box.
The Unit Control
Type configuration,
Configuration
--+UNIT---_U.(TL, defimlt value is for Thermostat (2) so there
is no need to configure this item.
Space
Temperature
Sensor
Control
--
Direct
Wired
(T-55 or T-56) -- Wire accessoryspace tempera-
ture sensor(s) to the T-55 terminals on the field connection
tenninat board located at the unit control box. Rel}r to Field-
Installed Accessories section.
The l_Mt Control
Type configuration,
Configuration
---_UNIT--_U.(TL, must be set to Space Sensor (3). The jumper
wire in the installer's packet must be connected bewveen R and
W1 for heating mode to operate.
Space
Temperature
Sensor
Control
--
CCN
(T-58)
-- Install the T-58 colrnnunicating thermostat. Con-
nect the CCN colrnnunication bus fiom the T-58 to the CCN
terminals on the field connection tenninat board located at the
unit control box. Configure the 48/50PG unit CCN communi-
cation element number, bus numbei; and baud rate. Configure
the T-58 thermostat CCN communication dement number and
also configure the T-58 with the 48/50PG unit element number.
The tMt
Control
Type configuration,
Configuration
---_UNIT--_U.(TL, must be set to Space Sensor (3). The jumper
wire in the instatler's packet must be connected bewveen R and
W1 for heating mode to operate.
Space
Temperature
Control
--
CCN
Link-
age -- The CCN colrnnunication must be properly configured
for the 48/50PG unit and all devices. Linkage configuration is
automatically done by the supervisory CCN Linkage device.
The Unit Control
Type configuration,
Configuration
---_UNIT---_U..CTL m ust be set to Space Sensor (3). The jumper
wire in the instalter's packet must be connected between R and
W1 for heating mode to operate.
Installation of an accessory supply air temperature (SAT)
sensor in the supply duct is recommended for Linkage applica-
tions. A supply duct SAT measurement is valid for heating
mode display, while the factory-standard internal SAT is not
valid for heating due to its location upstream of the heating sec-
tion. When installing the supply duct SAT, the heating mode
display is enabled by setting (bnfigm'ation---_HEAT---agAT.H
to ENBL.
Space
Humidity
Control
-- Humidistat
-- Wire
the Humidistat accessory to terminals Humidistat 1and 2 locat-
ed on the field connection tenninal strip in the bottom of the
control box. The Space Humidity Switch setting is located at
(bnfiguration--_Unit--_RH.SVK
The factory default for units
with Humidi-MiZer
TM
system is 1 (normally open).
Space
Humidity
Control
--
Thermidistat
TM
--
Wire the Thennidistat accessory Dehum output to tenninat
Humidistatl located on the field connection terminal strip in
the bottom of the control box. The Space Humidity Switch set-
ting is located at (bnfiguration-->Unit-->RH, gVKThe factory
default for units with Humidi-MiZer system is 1 (normally
open).
Space
Humidity
Control-
Relative
Humidity
Sensor
--
Wire the humidity sensor to terminals 3 () and
4 (+) located on the field connection terminal strip in the
bottom of the control box. The RH Sensor on OAQ Input set-
ting is located at (bnfigttration--_Unit--_RH.S.
The setting
must be configured to YES to use the relative humidity sensor.
CCN Communication
-- Configure
(bnfigttration-->
C(W_,C(DC_A to desired element number. (Default is 1.) Con-
l]gure
(bnfiguration_'(W_'CN.B
to desired bus number.
(Dethult is 0.) Configure (bnfiguration_'CN---_BAUD
to
desired code number for baud rate. (Default is 3
9600 baud.)
Accessories
-- See the Field-Installed Accessories sec-
tion, control connection tables, and CCN or Display parmneter
tables for required connections and configurations.
Service
Test
-- The Service Test function can be used to
verit)
proper operation
of compressors,
heating
stages,
indoor tan, outdoor _ans, power exhaust tans, economizer,
Humidi-MiZer system, and alann relay. Use of Selaqce Test is
recolrnnended at initial system start-up and during trouble-
shooting.
35