APPENDIX
B - VFD INFORMATION
(CONT)
Table 41 -- FAULT
CODES
FAULT
FAULT NAME IN PANEL
DESCRIPTION
AND RECOMMENDED
CORRECTIVE
ACTION
CODE
1
OVERCURRENT
Output current is excessive.
Check for excessive motor load, insufficient
acceleration
time (parameters
2202
ACCELER TIME 1, default 30 seconds), or faulty motor, motor cables or connections.
2
Intermediate
circuit DC voltage is excessive. Check for static or transient over voltages in the input power supply,
DC OVERVOLT
insufficient
deceleration
time (parameters
2203 DECELER TIME 1, default 30 seconds), or undersized
brake chopper
(if present).
3
DEV OVERTEMP
Drive heat sink is overheated.
Temperature
is at or above 115°C (239°F). Check for fan failure, obstructions
in the air
flow, dirt or dust coating on the heat sink, excessive ambient temperature,
or excessive motor load.
4
SHORT CIRC
Fault current. Check for short-circuit
in the motor cable(s) or motor or supply disturbances.
5
OVERLOAD
Inverter overload condition.
The drive output current exceeds the ratings.
5
DC OVERVOLT
Intermediate
circuit DC voltage is not sufficient.
Check for missing phase in the input power supply, blown fuse, or
under voltage on main circuit.
7
All LOSS
Analog input 1 loss. Analog input value is less than All FLT LIMIT (3021). Check source and connection
for analog
input and parameter
settings for All FLT LIMIT (3021) and 3001 AI<MIN
FUNCTION.
8
AI2 LOSS
Analog input 2 loss. Analog input value is less than AI2 FLT LIMIT (3022). Check source and connection
for analog
input and parameter
settings for AI2 FLT LIMIT (3022) and 3001 AI<MIN
FUNCTION.
9
MOT OVERTEMP
Motor is too hot, as estimated
by the drive. Check for overloaded
motor. Adjust the parameters
used for the estimate
(3005 through
3009). Check the temperature
sensors and Group 35 parameters.
10
Panel communication
is lost and either drive is in local control mode (the control panel displays
LOC), or drive is in
remote control mode (REM) and is parameterized
to accept start/stop,
direction
or reference from the control panel.
PANEL LOSS
To correct check the communication
lines and connections.
Check parameter
3002 PANEL COMM ERROR,
parameters
in Group 10: Command
Inputs and Group 11 :Reference
Select (if drive operation
is REM).
11
ID RUN FAIL
The motor ID run was not completed
successfully.
Check motor connections.
12
MOTOR STALL
Motor or process stall. Motor is operating
in the stall region. Check for excessive load or insufficient
motor power.
Check parameters
3010 through
3012.
13
RESERVED
Not used.
14
EXT FAULT 1
Digital input defined to report first external fault is active. See parameter
3003 EXTERNAL
FAULT 1.
15
EXT FAULT 2
Digital input defined to report second external fault is active. See parameter
3004 EXTERNAL
FAULT 2.
15
EARTH FAULT
The load on the input power system is out of balance.
Check for faults in the motor or motor cable. Verify that motor
cable does not exceed maximum
specified length.
17
UNDERLOAD
Motor load is lower than expected. Check for disconnected
load. Check parameters
3013 UNDERLOAD
FUNCTION
through
3015 UNDERLOAD
CURVE.
18
THERM FAIL
Internal fault. The thermistor
measuring
the internal temperature
of the drive is open or shorted.
Contact Carrier.
19
OPEX LINK
Internal fault. A communication-related
problem
has been detected between the OMIO and OINT boards. Contact
Carrier.
20
OPEX PWR
Internal fault. Low voltage condition detected on the OINT board. Contact Carrier.
21
CURR MEAS
Internal fault. Current measurement
is out of range. Contact Carrier.
22
SUPPLY PHASE
Ripple voltage in the DC link is too high. Check for missing main phase or blown fuse.
23
RESERVED
Not used.
24
Motor speed is greater than 120% of the larger (in magnitude)
of 2001 MINIMUM SPEED or 2002 MAXIMUM SPEED
OVERSPEED
parameters.
Check parameter
settings for 2001 and 2002. Check adequacy
of motor braking torque.
Check
applicability
of torque control.
Check brake chopper
and resistor.
25
RESERVED
Not used.
26
DRIVE ID
Internal fault. Configuration
block drive ID is not valid.
27
CONFIG FILE
Internal configuration
file has an error. Contact Carrier.
28
Field bus communication
has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT
SERIAL 1 ERR
TIME). Check communication
settings (Group 51 or 53 as appropriate).
Check for poor connections
and/or noise on
line.
29
EFB CON FILE
Error in reading the configuration
file for the field bus adapter.
30
FORCE TRIP
Fault trip forced by the field bus. See the field bus reference
literature.
31
EFB 1
Fault code reserved for the EFB protocol application.
The meaning is protocol
dependent.
32
EFB 2
Fault code reserved for the EFB protocol application.
The meaning is protocol
dependent.
33
EFB 3
Fault code reserved for the EFB protocol application.
The meaning is protocol
dependent.
34
MOTOR PHASE
Fault in the motor circuit. One of the motor phases is lost. Check for motor fault, motor cable fault, thermal relay fault,
or internal fault.
35
OUTP WIRING
Error in power wiring suspected.
Check that input power wired to drive output. Check for ground faults.
101-105
SYSTEM ERROR
Error internal to the drive. Contact Carrier and report the error number.
201-205
SYSTEM ERROR
Error internal to the drive. Contact Carrier and report the error number.
87