Modulation Board (Aux1) - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Modulation
Board
(AUX1)
The AUXI
board controls
the compressor
capacity
and the indoor
fan speed (See Fig. 18 and Table 21.)
It outputs
a l-5vdc
and a
2-10vdc
signal to the DSC
and VFD for capacity
and fan speed,
respectively.
This board
is also used as the LEN connection
buss
for
the
ECB,
therefore
must
be
operational
for the
ECB
to
communicate.
IMPORTANT:
The AUXI
board
has an 8-position
DIP switch
(SI)
that is factory
set for its LEN address.
All the switches
must
be in the off position
except 4, 5 and 7 which
are on (off is towards
the center of the board).
Do not change
this setting.
DIP SWITCH
TR1
TR2
TR3
TR4
TR5
TR(_
TR7
TR8
Fig. 18 - Modulation
Board
(AUX1)
(:08658
Table
21 -- AUX1 Connections
DISPLAY
CONNECTION
NAME
POINT DESCRIPTION
TYPE OF I/O
PIN NUMBER
OUTPUTS
Input power from TRAN1
24 VAC
J1, 11-12
CAPC
Compressor
Capacity
1-5vdc
CH9
RSPD
Commanded
Fan Speed
2-10vdc
CH10
COMMUNICATION
Local Equipment Network (LEN)
communication
J9, 1-3
Local Equipment Network (LEN)
communication
J9, 1-3
51