all units with Economizers:
1. 1.The
outdoor
temperature
is below
the Econo
Cool
Hi
Temp Limit (Configuration--_ECON--_EH_LO)
and above
the
Econo
Cool
Lo
Temp
Linfit
(C onfiguration--+
E CON--+ EL_LO) .
For units
with Enthalpy
Control
2. 1.The outdoor
enthalpy
is low and the outdoor
temperature
is
below
the
Econo
Cool
Hi
Temp
Limit
(Configuration--+ECON--+EH.LO)
and above
the Econo
Cool Lo Temp Limit (Configuration--+ECON--+EL.LO).
If the conditions
above are true and the economizer
is available for
cooling
the economizer
outside
air and return
air dampers
will
modulate
to allow proportions
of outside
air and return
air to mix
and produce
a temperature
equal to the Cool
Supply
Air Set Point
(Setpoint--+SASP).
If
reset
is
applied
to
the
Supply
Air
Temperature
Set Point (Setpoint--+SASP)
the dampers
will control
to the Supply Air Control
Point (Run
Status--+COOL--+SA.CP).
If the conditions
above are true but the economizer
dampers
are not
able to satisfy
the Cool
Supply
Air Set Point (Setpoint--+SASP)
with Reset (if applied), the compressor
will turn on and modulate
to provide
additional
cooling
to satisfy
the Cool
Supply
Air Set
Point (Setpoint--+SASP)
with Reset if applied.
If the conditions
above are not true, the economizer
will move to a
user
Configurable
Econ
Min
at
Max
Fan
Speed
(Configuration---,ECON---,MP_X)
where
the
nfinimum
economizer
damper
position
is based on the Supply Fan Maximum
Speed
(Configuration--+UNIT--+FS.MX).
This
is
done
to
maintain
a constant
airflow
through
the economizer
by opening
the
dampers
more
as the indoor
fan speed
is reduced
or closing
the
dampers
more as the indoor
fan speed increases.
The shape
of the Economizer
Minimum
Position
vs. Fan
Speed
curve is determined
by the configuration
parameters:
Econ Min at
25% Fan speed
(Configuration--+ECON--+MP.25),
Econ
Min at
50% Fan speed
(Configuration--+ECON--+MP.50),
Econ
Min at
75% Fan speed
(Configuration--+ECON--+MP.75)
and Econ Min
at Max Fan speed (Configuration---,ECON---,MP_X).
The
Econ
Min
at
25%
Fan
speed
(Configuration--+ECON--+MP.25),
Econ
Min at 50% Fan speed
(Configuration--+ECON--+MP.50)
and
Econ
Min
at 75%
Fan
speed
(Configuration--+ECON--+MP.75)
damper
positions
are
calculated
based
on
the
Econ
Min
at
Max
Fan
Speed
(Configuration---,ECON---,MP_X)
and
Supply
Fan
Maximum
Speed (Configuration---,UNIT---,FS_X).
The
Econ
Min
at
25%
Fan
speed
(Configuration--+ECON--+MP.25),
Econ
Min at 50% Fan speed
(Configuration--+ECON--+MP.50)
and
Econ
Min
at 75%
Fan
speed (Configuration--+ECON--+MP.75)
damper
position
are user
configurable
and can be determined
by setting the fan speed at 25,
50 and 75%
and determining
the damper
position
required
to
maintain
the
Econ
Min
at
Max
Fan
Speed
(Configuration--+ECON--+MP.MX)
Outside
air CFM through
the
economizer
outside
air
dampers.
The
default
calculations
programmed
into
the
PD
controls
is based
on
a side
shot
economizer
at 400 CFM/TON
Supply
Air flow with negative
0.25
in H20 pressure
in the return duct.
Econ Min at Max fan Speed (Configuration--+UNIT--+FS.MN)
is
set by user based
on minimum
required
outside
air ventilation
CFM required
for the application.
This
procedure
would
be the
same as if this were
a CV unit with the unit running
at the design
point
CFM.
This
determines
the minimum
position
amount
of
outside
air CFM
required
when
the fan is running
at maximum
speed.
Configure
the
Indoor
Fan
Max
Speed
CFM
(Configuration--+ECON--+IDF.C)
either
to
the
supply
CFM
deternfined
from
the fan performance
tables or air balance
reports.
If using
fan performance
tables make
corrections
for all installed
accessory
pressure
loss and use measured
RPM,
power
and static
pressure
readings
to deternfine
the actual Indoor
Fan Max Speed
CFM (Configuration--+ECON--+IDF.C).
Economizer
Position
%
MAX P
20 25
50
75
ECON
MIN
AT MAX
FANSPEED
POSITION
(MmNP MAX)
Minimum
Configurable
Fan Speed is 20%
4PMX
;v
AQ/dl'j
for DqYsj
I_
Fan Speed
%
100
MINIMUM
IAQ
DAMPER
POSITION
(AO. MN)
100
700
INSIDE/OUTSIDE CO2
/
DIFFERENTIAL
AQ
AQ
DIFFERENTIAL
DIFFERENTIAL
LOW (AQD.L)
HIGH (AQD.H)
C09145
Fig. 8 - Economizer
Minimum
Position
If the indoor fan is not operating, the econonfizer will be fully
closed, 0% open.
Ventilation Mode
If the space temperature falls 0.5F below the Occupied Cool Set
Point (Setpoints-+OCSP)
the compressor will turn off, the indoor
fan
speed
will
be
set
to
the
Vent
Mode
Fan
Speed
(Configuration-+UNIT-+FS.VM)
and the econonfizer will open
to the position that will supply nfinimum ventilation air at the
configured
Vent
Mode
Fan
Speed
(Configuration-+UNIT-+FS.VM).
Default Vent Mode Fan Speed
(Configuration-+UNIT-+FS.VM)
is 50%. Configuring the Vent
Mode Fan Speed (Configuration-+UNIT-+FS.VM)
lower will
provide
additional energy savings in vent mode but may not
supply the required ventilation air to the conditioned space at lower
fan speeds.
Demand Control Ventilation
The 48PD units can also be equipped with optional CO2 sensors
for additional indoor air quality control.
When unit is equipped
with a return duct CO2 sensor or return duct CO2 sensor and
outside air CO2 sensor the Econonfizer nfinimum position vs. fan
speed curve will be recalculated based on the CO2 level of the
return and/or outside air as shown in Fig. 8. See the Indoor Air