TheTXVis set
to maintain
between
10 and
15 degrees
of
superheat
at the compressors.
The valves are factory set and cannot
be adjusted.
Do not use A TXV designed
for use with R-22.
R410A
REFRIGERANT
OUTDOOR
FAN M UST BE OPERA TING
ON HIGH
SPEED
160
140
120
lOO
80 ¸
60
20
150
200
250
300
350
400
450
500
550
Compressor
Discharge
Pressure,
[psig]
160
Fig. 35 - Charging
Chart--
48/50PD05
R410A
REFRIGERANT
OUTDOOR
FAN
M UST
BE
OPERA
TING
ON
HIGH
SPEED
6OO
(07040
140
120
lOO
80 ¸
60
20
150
200
250
300
350
400
450
500
550
600
Compressor
Discharge
Pressure,
[psig]
Fig. 36 - Charging
Chart
48/50PD06
(07041
Puron®
Refrigerant
Puron refrigerant
operates
at 50 to 70 percent
higher pressures
than
R-22.
Be
sure
that
servicing
equipment
and
replacement
components
are designed
to operate
with Puron refrigerant.
Do not
mix with
components
that have been
used with
other refrigerants.
Puron refrigerant,
as with
other
HFCs,
is only
compatible
with
POE oils.
Recovery
cylinder
service
pressure
rating
must be 400 psig. Puron
systems
should
be
charged
with
liquid
refrigerant.
Use
a
commercial-type
metering
device
in the manifold
hose.
Manifold
sets should be 750 psig high-side
and 200 psig low-side
with 520
psig low-side
retard.
Use hoses
with
750
psig service
pressure
rating.
Leak
detectors
should
be
designed
to
detect
HFC
refrigerant.
Table 26 -- Altitude
Compensation*
48PG03-07
ELEVATION
NATURAL GAS
PROPANE
(It)
ORIFICEt
ORIFICEt
0-1,999
45
52
2,000
47
52
3,000
47
53
4,000
47
53
5,000
48
53
6,000
48
53
7,000
48
53
8,000
49
54
9,000
49
54
10,000
50
54
11,000
51
54
12,000
51
55
13,000
52
55
14,000
52
56
*As the height
above
sea level
increases,
there is less oxygen
per cubic foot of air.
Therefore,
heat input
rate should
be reduced
at higher
altitudes.
Includes
a 4% input
reduction
per each 1000 ft.
t
Orifices
available
through
your Carrier
dealer.
Gas Valve Adjustment
The gas valve
opens
and closes
in response
to the thermostat
or
limit control.
When power is supplied
to valve terminals
W2 (High Fire) and C1,
the main valve opens
to its preset position.
The regular factory
setting is stamped
on the valve body.
To adjust regulator:
1. Set unit at setting for no call for heat.
2. Turn main gas valve to OFF position.
3. Remove
1/8-in.
pipe
plug
from
manifold
pressure
tap
connection.
Install
a suitable
pressure-measuring
device.
4. Set main gas valve to ON position.
5. Set thermostat
at setting to call for heat.
6. Remove
screw
cap covering
regulator
adjustment
screw.
(See Fig. 37.)
7. Turn adjustment
screw clockwise
to increase
pressure
or
counterclockwise
to decrease
pressure.
The setting
is 3.50
in. wg on sizes 03-14
and 3.00 on size 16-28.
8. Once desired
pressure
is established,
set unit setting
for no
call
for
heat,
turn
off
main
gas
valve,
remove
pressure-measuring
device,
and replace
1/8-in. pipe plug and
screw cap.
HIGH REGULATOR
ADJUSTMENT
SCREW
LOW REGULATOR
ADJUSTMENTSCREW
OUTLETPRESSURE
HI (W2) MALE
INLET
PRESSURE
MAIN (Wl)
MALE
SPADE
TERMINAL
TAP
(PLUGGED)
SPADE
TERMINAL
Fig. 37 - 48PD
Gas Valve
(08663
65