APPENDIX
B - VFD INFORMATION
(CONT)
Table 42 -- ALARM
CODES
ALARM
ALARM NAME
DESCRIPTION
AND RECOMMENDED
CORRECTIVE
ACTION
CODE
IN PANEL
2001
-
Reserved
2002
-
Reserved
2003
-
Reserved
2004
DIR LOCK
The change
in direction
being attempted
is not allowed.
Do not attempt to change the direction
of motor rotation,
or
Change parameter
1003 DIRECTION to allow direction change
(if reverse operation
is safe).
Field bus communication
has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT
2005
I/O COMM
TIME). Check communication
settings (Group 51 or 53 as appropriate).
Check for poor connections
and/or noise on
line.
2006
All LOSS
Analog input 1 is lost, or value is less than the minimum
setting, Check input source and connections.
Check the
parameter
that sets the minimum
(3021) and the parameter
that sets the Alarm/Fault
operation
(3001).
2007
AI2 LOSS
Analog input 2 is lost, or value is less than the minimum
setting, Check input source and connections.
Check
parameter
that sets the minimum
(3022) and the parameter
that sets the Alarm/Fault
operation
(3001).
Panel communication
is lost and either the VFD is in local control mode (the control panel displays
HAND), or the
VFD is in remote control mode (AUTO) and is parameterized
to accept start/stop,
direction or reference from the
2008
PANEL LOSS
control panel, To correct, check the communication
lines and connections,
Parameter 3002 PANEL LOSS, and
parameters
in groups
10 COMMAND
INPUTS and 11 REFERENCE
SELECT (if drive operation
is REM).
2009
-
Reserved
Motor is hot, based on either the VFD estimate or on temperature
feedback,
This alarm warns that a Motor Overload
2010
MOT OVERTEMP
fault trip may be near, Check for overloaded
motor. Adjust the parameters
used for the estimate
(3005 through
3009).
Check the temperature
sensors and Group 35 parameters.
Motor load is lower than expected. This alarm warns that a Motor Underload
fault trip may be near. Check that the
2011
UNDERLOAD
motor and drive ratings match (motor is NOT undersized
for the drive). Check the settings on parameters
3013 to
3015.
2012
MOTOR STALL
Motor is operating
in the stall region. This alarm warns that a Motor Stall fault trip may be near.
This alarm warns that the drive is about to perform an automatic fault reset, which may start the motor. To
2013*
AUTORESET
control automatic
reset, use parameter
group 31 (AUTOMATIC RESET).
This alarm warns that the PFA autochange
function
is active. To control PFA, use parameter
group 81 (PFA) and the
2014
AUTOCHANGE
Pump Alternation
macro.
This alarm warns that the PFA interlocks are active, which means that the drive cannot start any motor (when
2015
PFA INTERLOCK
Autochange
is used), or a speed regulated
motor (when Autochange
is not used).
2016
-
Reserved
2017"
OFF BUTTON
This alarm indicates that the OFF button has been pressed.
This alarm warns that the PID sleep function
is active, which means that the motor could accelerate
when the PID
2018
PID SLEEP
sleep function ends. To control PID sleep, use parameters
4022 through
4026 or 4122 through
4126.
2019
ID RUN
The VFD is performing
an ID run.
2020
OVERRIDE
Override mode is activated.
START ENABLE 1
This alarm warns that the Start Enable 1 signal is missing. To control Start Enable 1 function,
use parameter
1608. To
2021
MISSING
correct, check the digital input configuration
and the communication
settings.
START ENABLE 2
This alarm warns that the Start Enable 2 signal is missing. To control Start Enable 2 function,
use parameter1609.
To
2022
MISSING
correct, check the digital input configuration
and the communication
settings.
2023
EMERGENCY
STOP
Emergency
stop is activated.
This alarm
is not indicated
by a relay
output,
even
when
the relay
output
is configured
to indicate
alarm
conditions,
parameter
1401
RELAY
OUTPUT
= 5 (ALARM)
or 16
FLT/ALARM).
Table 43 -- MAINTENANCE
INTERVALS
MAINTENANCE
INTERVAL
Heat sink temperature
check and
Every 6 to 12 months (depending
cleaning
on the dustiness
of the
environment)
Main cooling fan replacement
Every five years
HVAC Control panel battery change
Every ten years
89