Carrier 50PD05 Operating And Service Instructions page 56

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Scrolling
Marquee
Display
This
device
is the
keypad
interface
used
to
access
rooftop
information,
read sensor
values,
and test the unit.
(See Fig. 23.)
The Scrolling
Marquee
display
is a 4-key, 4-character,
16-segment
LED (light-emitting
diode) display.
Eleven
mode LEDs are located
on the display
as well as an Alarm
Status LED. See Basic Control
Usage section
for further
details.
Alarm
St alus
80,;2°0 :2
80:::,:
.......
Fig. 23 - Scrolling
Marquee
(06320
Accessory
Navigator
TM
Display
The
accessory
hand-held
Navigator
display
can be
used
with
48/50PD
units.
(See Fig. 24.) The Navigator
display
operates
the
same way as the Scrolling
Marquee
device.
The Navigator
display
plugs into the LEN port on either TB or the ECB board.
Fig. 24 - Accessory
Navigator
TM
Display
C06321
Carrier
Comfort
Network
(CCN)®
Interface
The
units
can be connected
to the CCN
if desired.
The
communication
bus wiring is a shielded, 3-conductor cable with
drain wire and is field supplied and installed. The system elements
are connected
to the communication
bus in a daisy chain
arrangement.
(See Fig. 25.) The positive
pin of each system
element communication
connector must be wired to the positive
pins of the system elements on either side of it. This is also
required for the negative and signal ground pins of each system
element. Wiring connections for CCN should be made at TB. (See
Fig. 25.) Consult
the CCN
Contractor's
Manual
for further
information.
IMPORTANT:
Conductors
and drain wire must be 20 AWG
(American
Wire
Gauge)
minimum
stranded,
tinned
copper.
Individual conductors must be insulated with PVC, PVC/nylon,
vinyl, Teflon, or polyethylene.
An aluminum/polyester
100% foil
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or
Teflon with a minimum operating temperature range of -20°C to
60 °C is required. See Table below for acceptable wiring.
MANUFACTURER
PART NO.
Alpha
2413 or 5463
Belden
8772
Carol
C2528
West Penn
302
It is important
when connecting
to a CCN communication
bus that
a color-coding
scheme
be used for the entire network
to simplify
the installation.
It is recommended
that red be used for the signal
positive,
black
for the signal
negative
and white
for the signal
ground.
Use
a similar
scheme
for
cables
containing
different
colored
wires.
At each
system
element,
the
shields
of its communication
bus
cables
must be tied together.
The shield screw on TBI can be used
to tie the cables
together.
If the communication
bus is entirely
within
one
building,
the
resulting
continuous
shield
must
be
connected
to a ground
at one point only. The shield screw on TBI
is not acceptable
for grounding.
If the communication
bus cable
exits
from
one building
and enters
another,
the shields
must
be
connected
to grounds
at the lightning
suppressor
in each building
where the cable enters or exits the building
(one point per building
only).
To connect
the unit to the network:
1. Turn off power
to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
(ground),
and black
(-) conductors.
(Substitute
appropriate
colors for different
colored
cables.)
3. Connect
the red wire to (+) terminal
on TBI,
the white wire
to COM terminal,
and the black wire to the (-) terminal.
4. The RJI4
CCN connector
on TBI
can also be used,
but is
only
intended
for temporary
connection
(for
example,
a
laptop computer
running
Carrier network
software).
5. Restore
power
to unit.
IMPORTANT:
A shorted
CCN
bus
cable
will
prevent
some
routines
from
running
and may prevent
the unit from
starting.
If
abnormal
conditions
occur,
unplug
the connector.
If conditions
return
to normal,
check
the CCN connector
and cable.
Run new
cable
if necessary.
A short
in one section
of the bus can cause
problems
with all system
elements
on the bus.
Field-Installed
Accessories
Space
Temperature
Sensor
(T-55)
The T-55
space temperature
sensor
(part no. 33ZCT55SPT)
is a
field-installed
accessory.
The
sensor
is installed
on
a building
interior
wall to measure
room
air temperature.
The T-55
sensor
also includes
an override
button
on the
front
cover
to permit
occupants
to override
the Unoccupied
Schedule
(if programmed).
TBI-T55-1
........
Sensor Input
TBI-T55-2
........
Sensor Common
Space
Temperature
Sensor
(T-56)
The T-56
space temperature
sensor
(part no. 33ZCT56SPT)
is a
field-installed
accessory.
This sensor includes
a sliding
scale on the
front cover that permits
an occupant
to adjust the space temperature
set point
remotely.
The
T-56
sensor
also includes
an override
button
on the
front
cover
to allow
occupants
to override
the
unoccupied
schedule
(if programmed).
TB1-T55-1
........
Sensor Input
TB1-T55-2
........
Sensor Common
TB1-T55-3
........
Setpoint
Offset Input
56

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0550pd0648pd06

Table of Contents