Indoor Air Quality (Iaq) - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

a.
(Configuration--,ECON--,UEFC
= O) - Disabled
When UEFC = 0, unoccupied
free cooling
is disabled.
Cooling
will only occur if the space exceeds
the
unoccupied
setpoints.
b. (Configuration--_ECON--_UEFC
= 1) - Unoccupied
When UEFC is set to 1, unoccupied
free cooling
can
occur throughout
the entire unoccupied
period.
The
space temperature
nmst be higher
then the nfid-point
between
the occupied
cooling
and heating
set points.
c. (Configuration--_ECON--_UEFC
= 2) - Preoccupancy
When UEFC is set to 2, unoccupied
free cooling
can
only occur when the time until the next occupied
period
is less than the Free Cool PreOcc
Time (FC.TM)
in
nfinutes.
2. Free
Cool
PreOcc
Time
(C onfiguratio
n--_ E CON--_ F C. TM)
FC.TM
is the configuration
that determines
how
many
minutes
before
occupancy
that free cooling
can occur when
set for Preoccupancy
(UEFC
= 2).
3. l.Free
Cool
Low
Temp
Linfit
(Configuration---,ECON---,FC.LO)
Unoccupied
free cooling
cannot
occur
if the Outdoor
Air
Temperature
(Temperature---,
AIR.T--,
OAT)
is less than
FCJLO.
Power
Exhaust
To
enable
power
exhaust
set
Power
Exhaust
Installed
(Configuration--_ECON--_PE_N)
to YES.
On the 48/50PD-05
and 06 size units both power
exhaust
fans are wired together
and
are controlled
by the configuration
Power
Exhaust
Stagel
CFM
(Configuration-_ECON-_PE1.C).
When
the Indoor
Fan
Max
Speed CFM (Configuration-_ECON-_IDF.C)
is set to the correct
supply
duct
CFM (either
by fan tables
or air balance
report)
the
control
will calculate
the outside
air CFM based
on outside
air
damper
position
and
Commanded
Fan
Speed
(Outputs-,FANS-,F.SPD)
to turn on the power exhaust
when the
calculated
outside
air CFM reaches
Power
Exhaust
Stage1
CFM
(Configuration--,ECON--,PE1.C).
The power
exhaust
will turn
off when
the
calculated
outside
air
CFM
falls
below
Power
Exhaust
Stagel
CFM
(Configuration--+ECON--+PE1.C).
The
Power Exhaust
Stage2
CFM (Configuration--+ECON--+PE2.C)
is
not currently
used on the 48/50PD-05
and 06 units.
Indoor
Air
Quality
(IAQ)
The
ComfortLink
TM
control
has
the
capability
for
several
methods
of demand
ventilation
control.
Indoor
air quality
is
typically
measured
using
a CO2
sensor whose
measurements
are
displayed
in parts per million
(ppm).
Outdoor
air quality
may be
measured
with
a CO2
sensor
for
indoor-outdoor
differential
demand
ventilation
control,
or with
other
sensor
types
for the
outdoor
air lockout
function.
The factory-installed
indoor
air
quality
CO2
sensor
is mounted
in
the
return
section.
A
field-installed
indoor
air quality
CO2 sensor
may be mounted
in
the return or directly
in the occupied
space, per job requirements.
The indoor
air quality
modes
of operation
can be affected
by the
IAQ
Analog
Input
Config
(Configuration---,
AIR.Q---,
IA.CF),
IAQ
Switch
Input
Config
(Configuration---,
AIR.Q---,
IA.CF),
OAQ
Analog
Input
Config
(Configuration---,
AIR.Q---,
OA.CF)
and other related fan and limit configurations
as described
below.
IAQ (Analog
Input)
The ComfortLink
TM control
is configured
for indoor
air quality
sensors
which
provide
4 to 20 mA signal for 0 to 2000 ppm CO2.
If the sensor
being
used
has a different
range,
the ppm
display
range
must
be reconfigured
by entering
new values
for the IAQ
Sensor
Value at 4mA
(Configuration--_AIR.Q--_L4M)
and IAQ
Sensor Value at 20mA
(Configuration--_AIR.Q--_L2OM).
IA.CF = 0 (No IAQ)
IA.CF
= 0 signifies
that there is no IAQ sensor
installed.
The
damper
will
operate
at the
Econ
Min
at Max
Fan
Speed
(Configuration--+ECON--+MP.MX)
when the fan is at Supply
Fan
Maximum
Speed
(Configuration---,UNIT---,FS_X)
and
the
damper
position
will vary
at other
fan speeds
as described
in the
Cooling
Mode with
Economizer
section
below
when
the space is
occupied
and the indoor
fan is on.
IA.CF
= 1 (DCV)
When
IA.CF
= 1 the IAQ
algorithm
is set for Demand
Control
Ventilation
(DCV).
During
DCV, the damper
modulates
between
two user configurations
depending
upon the relationship
between
the Indoor Air Quality
(IAQ) and the Outdoor
Air Quality
(OAQ).
The lower of these two positions
is referred
to as the Econo
Min
IAQ Position
(Configuration--+AIR.Q--+AQ.MN)
while the higher
is
referred
to
as
the
Econ
Min
at
Max
Fan
Speed
(Configuration---,ECON---,MP_X).
The
Econo
Min
IAQ
Position
(Configuration--+AIR.Q--+AQ.MN)
should
be set to an
economizer
position
that brings
in enough
fresh
air to remove
contaminates
and CO2
generated
by sources
other
than people.
The
Econ
Min
at
Max
Fan
Speed
(Configuration--+ECON---,MP.MX)
should
be
set
to
an
economizer
position
that brings
in fresh air to remove contaminates
and CO2
generated
by all sources
including
people
when
the
indoor
fan is operating
at the
Supply
Fan
Maximum
Speed
(Configuration--+UNIT--+FS.MX).
The Econ
Min at Max
Fan
Speed
(Configuration---,ECON---,MP_X)
value
is the
design
value for n_axinmm
occupancy.
The ComfortLink
TM control
will begin
to open the damper
from
the Econo
Min IAQ Position
(Configuration---,AIR.Q---,AQd_N)
position
when
the IAQ
level
begins
to exceed
the Outdoor
Air
Quality
(OAQ)
level by a configuraMe
amount.
This amount
is
referred
to
as
AQ
Differential
Low
(Configuration--+AIR.Q--+AQD_L).
When
the
differential
between
IAQ
and
OAQ
reaches
AQ
Differential
High
(Configuration--+AIR.Q--+AQDJI),
the economizer
position
will
be
at
the
Econ
Min
at
Max
Fan
Speed
(Configuration---,ECON---,MP_X)
when
the indoor
fan speed is
at
Supply
Fan
Maximum
Speed
(Configuration---,UNIT---,FS_X).
When
the
IAQ/OAQ
differential
is
between
AQ
Differential
Low
(Configuration--+AIR.Q--+A
QD.L)
(Con figuration--+AIR.Q--+A
QD JI) ,
damper
between
Econ
Min
(Configuration--+ECON--+MP.MX)
(Configuration--+AIR.Q--+A
Q.MN)
in Figure
3.
At other
fan speeds
and
AQ
Differential
High
the control
will modulate
the
at
Max
Fan
Speed
and Econo Min IAQ Position
in a linear manner
as shown
the
econonfizer
damper
will
operate
in the shaded
area between
the two econonfizer
position
curves
but at the actual fan speed as indicated
by Commanded
Fan
Speed (Outputs-,FANS-,F.SPD).
IA.CF
= 2 (Override
IAQ)
When IA.CF
= 2, the IAQ algorithm
maintains
the damper
at Econ
Min at Max Fan Speed
(Configuration--,ECON--,MP.MX)
when
the
indoor
fan
speed
is
at
Supply
Fan
Maximum
Speed
(Configuration--,UNIT--,FS.MX)
or in the shaded
area of Figure
3 when
the indoor
fan speed
is at the Commanded
Fan Speed
(Outputs-,FANS-,F.SPD)
until
the override
condition
triggers.
The override
triggers
when
the IAQ/OAQ
differential
is greater
than
AQ
Differential
High
(Configuration--+AIR.Q--+AQD.H).
The
IAQ
Override
Position
(Configuration--+AIR.Q--+OVRaP).
The economizer
damper
will return to the Econ
Min at Max Fan
Speed
(Configuration---,ECON---,MP_X)
or MP.MX
curve
at
other
fan speeds
when
the IAQ/OAQ
differential
is less than the
AQ Differential
Low (Configuration--+AIR.Q--+AQD.L).
The
override
algorithm
will
operate
whenever
the
building
is
occupied
and the indoor
fan is operating
or whenever
the IAQ
algorithm
has caused the indoor
fan to operate.
The IAQ Analog
Fan Config
(Configuration--+AIR.Q--+IA.FN)
determines
whether
or not the IAQ algorithm
can turn on the indoor
fan.
If the indoor
fan is not operating,
the economizer
position
will be
zero.
If the override
is not active and the building
is unoccupied,
the economizer
position
will be zero.
The damper
position
may
16