Alarm Handling; Troubleshooting; Complete Unit Stoppage; Restart Procedure - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Loadshed
Group
Number
(S.GRP)
This corresponds to the loadshed supervisory devices that reside
elsewhere on the CCN network and broadcast loadshed and redline
commands to its associated equipment parts. This variable will
default to zero which is an invalid group number. This allows the
loadshed flmction to be disabled until configured.
Redline
Max Capacity
(R.MXC)
This
configuration
tells
the
unit
the
maximum
cooling/dehunfidification
capacity
allowed
active
during
a
loadshed condition.
Redline
Max Heat Stages
(R.MXH)
This configuration
tells the unit the maximum
heating stages
allowed to be on during a redline condition.
Loadshed
Max Heat
Stages (R.MXH
This configuration
tells the unit the maximum
heating stages
allowed to be on during a loadshed condition.
The two Demand Linfiting methods can be active simultaneously.
The lowest cool capacity and heat stage linfits imposed by either
method are applied, and these "effective linfits" are shown in the
points
CAPLIMIT
(Run
Status--+COOL--+LMT.C)
and
HSTGLIMT
(Run
Status--+HEAT--+LMTJt),
respectively.
In
normal running mode, these limits will prevent capacity/stages
from being added, or capacity/stages to be removed, as applicable.
In test mode, these limits are ignored, and the user may continue to
operate at full load.
The point MODEDMDL
(Run Status--+MODE--+DJ, MT) is used
to show if any Demand Limiting is in effect that prevents the unit
from operating either cooling or heating at full-capacity.
IMPORTANT:
MODEDMDL
may reflect that staging is NOT
limited even though Loadshed is active or the network points are
being forced, if the capacity/stage limits in effect are not less than
the capacity/stages present in the unit.
If a more drastic mode of Demand Limiting
is required, the
network point HVACDOWN (Run Status--+MODE--+HV.DN)
can
be used to prohibit the unit from selecting any HVAC mode, thus
preventing the operation of the supply fan, compressors, condenser
fans, and heat stages. This point must also be forced, and is reset
automatically when not forced, and at POR.
Alarm
Handling
There are a variety of different alerts and alarms in the system.
Alerts are indicated by TXXX (where XXX is the alert number) on
the display and generally signify that the improperly functioning
circuit can restart without human interaction. If an alarm occurs,
indicated by AXXX (where XXX is the alarm number), the
damaged circuit will generally not restart without an alarm reset via
the Scrolling Marquee display or CCN.
The response of the control system to various alerts and alarms
depends on the seriousness of the particular alert or alarm. In the
mildest case, an alert does not affect the operation of the unit in any
manner. An alert can also cause a "strike." A "striking" alert will
cause the circuit to shut down for 15 minutes. This feature reduces
the likelihood of false alarms causing a properly working system to
be shut down incorrectly. If three strikes occur before the circuit
has an opportunity to show that it can flmction properly, the circuit
will strike out, causing the shutdown
alarm for that particular
circuit. Once activated, the shutdown alarm can only be cleared via
an alarm reset.
However, circuits with strikes will be given an opportunity to reset
their strike counter to zero. As discussed above, a strike typically
causes the circuit to shut down. Fifteen nfinutes later, that circuit
will once again be allowed to run. If the circuit is able to run for 1
nfinute, its replacement circuit will be allowed to shut down (if not
required
to run to satisfy
requested
stages).
However,
the
"troubled" circuit must run continuously
for a user defined time
(Configuration-+COOL-+RST.C)
with no detectable
problems
before
the strike
counter
will be reset to zero. Default
value
is 5
nfinutes.
CCN
Alarm
Broadcast
Operators
of CCN
networks
nfight
not want
to be notified
of
"striking"
alerts
for refrigerant
circuits
until
the circuit
has been
shut down
due to 3 strikes.
Set the cooling
configuration
of Alert
Each
Strike
(Configuration--+COOL--+ALM.N
on
display,
ALM_NOW
on CCN) to YES to broadcast
each circuit strike alert.
Set Alert Each Strike to NO to broadcast
only circuit
shut down.
Alert Each Strike configuration
is ignored
during
Service
Test and
all alerts are broadcast.
Alarm Relay Output
The alarm relay output is a normally
open 24 vac output between
field connection
terminal board
terminals
C and X. Selection
of
which
alerts and alarms will result
in closing
of the alarm relay
may
be
set
in
the
Alarm
Relay
Configuration
(Configuration--,ALM.O).
Setting
a configuration
to YES
will
result
in the alarm output
relay, ALRM,
status of ON and 24 vac
between
C and X when
that particular
condition
is in an alarm
state.
Setting
a configuration
to NO will result in no action by the
alarm output relay for that particular
condition.
IMPORTANT:
An accessory
filter switch can be used along with
the alarm relay output function
to indicate
dirty filter service need.
See the Troubleshooting
section
for more information
on viewing,
diagnosing,
and clearing
alerts and alarms.
TROUBLESHOOTING
The
Scrolling
Marquee
display
shows
the
actual
operating
conditions
of the unit while
it is running.
If there
are alarms
or
there have been alarms,
they will be displayed
in either the current
alarm list or the history
alarm list. (See Table 8.) The Service
Test
mode
allows
proper
operation
of the compressors,
fans, and other
components
to be checked
while
the unit is not operating.
See
Service Test.
Complete
Unit Stoppage
There
are several
conditions
that can cause the unit not to provide
heating
or cooling:
• If an alarm is active which causes the unit to shut down,
diagnose
the problem
using the information
provided
in Alarms
and Alerts section below.
• Cooling
and heating
loads are satisfied.
• Programmed
occupancy
schedule.
• General
power failure.
• Tripped
CB1 or CB2 (24-volt
transformer
circuit breakers).
• Unit is turned off through
the CCN network.
• If outdoor-air
temperature
is less than the Compressor
Lockout
Temperature
(CA.LO)
configuration
value, unit cannot cool.
• If outdoor-air
temperature
is greater than the Heating
Lockout
Temperature
(HT_LO) configuration
value, unit cannot heat.
Restart
Procedure
Before
attempting
to restart
the machine,
check
the alarm
list to
determine
the cause of the shut down.
If the shutdown
alarm for a
particular
control
function
has occurred,
deternfine
and correct
the
cause
before allowing
the unit to run under its own control
again.
When
there
is problem,
the unit should
be diagnosed
in Service
Test mode.
The alarms
nmst be reset before
the control
function
can operate
in either Normal
mode or Service
Test mode.
Control
Module
Communication
Red LED
Proper
operation
of the MBB, ECB
and AUX1
control boards
can
be visually
checked
by looking
at the red status
LEDs.
When
operating
correctly,
the red status LEDs should blink
in unison
at a
rate
of once
every
2 seconds.
If the red LED
on the ECB
and
24

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0550pd0648pd06

Table of Contents