Carrier 50PD05 Operating And Service Instructions page 103

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

ITEM
AIR.Q
IA.CF
IA.FN
II.CF
II.FN
AQ.MN
OVR.P
OA.CF
OAQ.L
AQD.L
AQD.H
DF.ON
DF.OF
1.4M
1.20M
O.4M
O.20M
H.4M
H.20M
ALM.O
A.SPC
A.SRT
A.OAT
A.CS
A.CMP
A.CKT
A.SSP
A.SCT
A.FAN
A.FIL
A.ECO
PID
EC.P
EC.I
EC.D
EC.DT
E.DBD
CRP
CRI
CRD
CRDT
LK.P
LK.I
LK.D
LK.DT
Table 65 -- MODE - CONFIGURATION
(cont)
EXPANSION
Air Quality
Config.
IAQ Analog
Input
Config
IAQ Analog
Fan Config
IAQ Switch
Input Config
IAQ Switch
Fan Config
Econo
Min IAQ Position
IAQ Override
Position
OAQ Analog
Input Config
OAQ Lockout
Limit
AQ Differential
Low
AQ Differential
High
Fan On AQ Differential
Fan Off AQ Differential
IAQ Sensor
Value at 4mA
IAQ Sensor
Value at 20mA
OAQ Sensor Value at 4mA
OAQ Sensor Value at
20mA
RH Sensor
Value at 4mA
RH Sensor
Value at 20mA
Alarm
Relay Config.
SPT/SPRH
Sensor
Failure
SAT/RAT
Sensor
Failure
OAT Thermistor
Failure
Current
Sensor
Failure
Compressor
Failure
Refrig Circuit
Failure
SSP Transducer
Failure
SCT Thermistor
Failure
Indoor
Fan Failure
Dirty Filter
Economizer
Failure
PID Configurations
Economizer
PID -
kP
Economizer
PID -
kl
Economizer
PID -
kD
Economizer
PID -
rate
Economizer
PID
Deadband
Capacity
PID - kP
Capacity
PID - kl
Capacity
PID - kD
Capacity
PID - rate
Linkage
Staging
PID - kP
Linkage
Staging
PID - kl
Linkage
Staging
PID - kD
Linkage
Staging
PID -
rate
RANGE
UNITS
DEFAULT
%
10
%
100
0
0: no FlOP
1: FlOP
0
0
6OO
100
7OO
6OO
2OO
0
2000
0
2000
0=No
IAQ
1 = DCV
2=Override
IAQ
3=Ctrl
Min Pos
0 = Neve r
1 =Occupied
2=Always
0=No
IAQ
1 = DCV N/O
2 = DCV N/C
3=Override
N/O
4=Override
N/C
0 = Neve r
1 =Occupied
2=Always
0to
100
0to
100
0=No
OAQ
1 = DCV
2=Lockout
OAQ
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 50
%
0
60 to 100
%
100
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
No
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
Yes/No
Yes
0.0 to 99.9
2.5
0.0 to 99.9
0.1
0.0 to 99.9
1
10.0 to 180.0
sec
15
0 to 25
%
3
CON
TABLE/SUB-TABLE
IAQ
CFG
ALM
CFG
CCN POINT
IAQANCFG
IAQANFAN
IAQINCFG
0 to 99.9
1.5
0 to 99.9
0.1
0 to 99.9
1
1 to 30
secs
5
0.0 to 99.9
10
0.0 to 99.9
5
0.0 to 99.9
5
10.0 to 180.0
secs
30
PID
CFG
IAQINFAN
IAQMINP
IAQOVPOS
OAQANCFG
OAQLOCK
DAQ
LOW
DAQ
HIGH
DAQFNON
DAQFNOFF
IAQ 4MA
IAQ_20MA
OAQ_4MA
OAQ
20MA
RH 4MA
RH 20MA
SPACE
AL
SATRATAL
OAT
AL
CS AL
COMP
AL
CKT
AL
SSP
AL
SCT
AL
FAN AL
FILT AL
ECON
AL
ECONO
P
ECONO
I
ECONO
D
ECONO
DT
ECONBAND
VCAP
P
VCAP
I
VCAP
D
VCAP
DT
LINK
P
LINK
I
LINK
D
LINK
DT
ENTRY
103