Carrier 50PD05 Operating And Service Instructions page 66

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

High Altitude
For high altitude applications
greater
than 2,000 ft the heat input
rate should be reduced.
The higher
the altitude
is above sea level,
the less oxygen
is in the air. See Table 8 for orifice
sizing.
A high
altitude
kit is available
to convert
unit for altitudes
up to 7,000 ft.
Main Burners
For all applications, main burners are factory set and should require
no adjustment.
Main Burner
Removal
1. Shut off (field-supplied)
manual
main gas valve.
2. Shut off power
to unit.
3. Open gas section
access door.
4. Disconnect
gas piping
from gas valve inlet.
5. Remove
wires from gas valve.
6. Remove
wires from rollout switch.
7. Remove
sensor wire and ignitor
cable from IGC board.
8. Remove
2 screws that hold the burner
assembly
to vestibule
plate.
9. Rotate
the burner/manifold
assembly
to the right,
away
from
the flue extension
and lift burner/manifold
assembly
out of unit.
Cleaning
and
Adjustment
1. Remove
burner
rack from unit as described
in Main Burner
Removal
section
above.
2. Inspect burners,
and if dirty, remove burners
from rack. The
two outer
burners
have the flame
crossover
closed
off in
order
to prevent
gas flow
from
exiting
the sides
of the
burner
assembly.
To prevent
ignition
problems,
make sure
the outer burners
are returned
to their original
position
when
done servicing.
3. Using
a soft
brush,
clean
burners
and crossover
port
as
required.
4. Adjust
spark gap. (See Fig. 38.)
5. Reinstall
burners
on rack.
6. Reinstall
burner
rack as described
above.
t
B
MA×.(_P. I
SECTION
E-E
SCALE
2:1
SPARK
GAP
_C
D_
_
SPARK
GAP
0.120 TO 0.140"
............
[3.05 TO 3.56]
SECTION
O-O
I
SECTION
A-A
SCALE
1:1
I
r
SECTION
B-B
SCALE
1:1
Fig. 38 - Spark
Gap Adjustment
SECTION
D-D
/
/
C06269
Filter Drier
Replace
filter drier
whenever
refrigerant
system
is exposed
to
atmosphere.
Only use factory
specified
liquid-line
filter driers with
working
pressures
no
less
than
650
psig.
Do
not
install
a
suction-line
filter drier
in liquid
line.
A liquid-line
filter drier
designed
for use with Puron®
refrigerant
is required
on every unit.
Protective
Devices
Compressor
Rotation
Overcurrent
Each compressor has internal line break motor protection.
Overtemperature
Each compressor has an internal protector to protect it against
excessively high discharge gas temperatures.
High-Pressure
Switch
If the high-pressure
switch
trips,
the compressor
will shut down
and the current
sensor (3-phase
units only) will not detect current.
See the Current
Sensor section below
for more information.
Current
Sensor
(CS) (3-Phase
Units Only)
The purpose
of the CS is to detect losses
in compressor
power.
After detecting
a loss in compressor
power,
unit control
locks out
the compressor
for 15 minutes.
After 15 minutes,
the alarm will
automatically
reset. If this alarm occurs
3 times consecutively,
the
compressor
will remain
locked
out until an alarm reset is initiated
via
CCN
or manually
via
the
Scrolling
Marquee
display
(see
Alarms
and Alerts section for more details).
IMPORTANT:
The current
sensor
is not currently
used
in the
48/50PD,
but reserved
for future implementation.
66

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0550pd0648pd06

Table of Contents