Carrier 50PD05 Operating And Service Instructions page 86

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

History
For reference,
the last three fault codes are stored
into parameters
0401,
0412,
0413.
For
the
most
recent
fault
(identified
by
parameter
0401),
the drive
stores
additional
data (in parameters
0402
through
0411)
to aid
in troubleshooting
a problem.
For
example,
a parameter
0404 stores the motor speed at the time of the
fault.
To clear the fault history
(all of Group
04, Fault
History
parameters),
follow these steps:
1. In the
control
panel,
Parameters
mode,
select
parameter
0401.
2. Press EDIT.
3. Press the UP and DOWN
buttons
simultaneously.
4. Press SAVE.
Correcting
Alarms
To correct
alarms,
first
determine
if the
Alarm
requires
any
corrective
action
(action
is not always
required).
Use Table 42 to
find and address
the root cause of the problem.
If diagnostics
troubleshooting
has determined
that
the
drive
is
defective
during
the warranty
period,
contact
ABB
Automation
Inc.,
at
1-800-435-7365,
option
4,
option
3.
A
qualified
technician
will review
the problem
with
the caller
and make
a
determination
regarding
how
to
proceed.
This
may
involve
dispatching
a designated
service
station (DSS)
representative
from
an authorized
station,
dispatching
a replacement
unit, or advising
return for repair.
VFD Maintenance
If installed in an appropriate environment,
the VFD requires very
little maintenance.
Table 43 lists the routine maintenance intervals recommended
by
Carrier.
Heat
Sink
The heat sink fins accumulate dust from the cooling air. Since a
dusty sink is less efficient at cooling the drive, overtemperature
faults become more likely. In a normal environment check the heat
sink annually, in a dusty environment check more often.
Check the heat sink as follows (when necessary):
1. Remove power from drive.
2. Remove the cooling fan.
3. Blow clean compressed air (not hunfid) from bottom to top
and simultaneously use a vacuum cleaner at the air outlet to
trap the dust. If there a risk of the dust entering adjoining
equipment, perform the cleaning in another room.
4. Replace the cooling fan.
5. Restore power.
86

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0550pd0648pd06

Table of Contents