Thermistor Troubleshooting - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Thermistor
Troubleshooting
The electronic control uses thermistors to sense temperatures used
to control operation of the unit. Resistances at various temperatures
are listed in Table 15-17. Thermistor pin connection points are
shown in the Maior System Components
section. The general
locations
of the thermistors are shown
the Maior
System
Components section.
Air Temperatures
Air temperatures are measured with 10 kilo-ohm thermistors. This
includes supply-air
temperature
(SAT), outdoor-air
temperature
(OAT), space temperature sensors (T55, T56, T58), and return air
temperature (RAT).
The supply air temperature (SAT), return air temperature (RAT)
and outdoor air temperature (OAT) thermistors use a snap-mount to
attach through the unit sheet metal panels. The snap-mount tabs
must be flattened on the tip end of the sensor to release for removal
from the panel.
(See Fig. 10.) To reinstall, make
sure the
snap-mount tabs extend out.
,,
",,,
!
/\
ix),
%
I
', ','_ \
%,, _d,',,/
\ '-\\ "%'7"g
\
\
\
%
\\
\
", ",-',',""L/"',,
X
JX
\
X
\x._=j
\\
\
_
\_X\\ %%%%
\\
(07015
Fig. 10 - SAT, RAT and OAT Thermistor
Mounting
Refrigerant Temperatures
Condenser
coil
temperatures
are measured
with
5 kilo-ohm
thermistors.
These measurements
provide
an approximate
saturated
condensing
temperature
for each circuit (SCT.A).
Fig. 11 shows
the factory
locations
for the SCT thermistors
on 48/50PD
units.
Ensure
that thermistors
are placed
at the correct location
and are
snapped
securely
over
the return
bend
so that contact
is made
between
the thermistor and the tube.
(07016
Fig. 11 - Saturated
Condensing
Temperature
Thermistor
Location
Thermistor/Temperature
Sensor
Check
A high quality digital volt-ohmmeter is required to perform this
check.
Connect the digital voltmeter across the appropriate thermistor
terminals at the J8 terminal strip on the Main Base Board (see
Maior System Components section).
Using the voltage reading obtained, read the sensor temperature
from Table 15-17.
To check thermistor
accuracy,
measure temperature
at probe
location
with
an
accurate
thermocouple-type
temperature-measuring
instrument. Insulate thermocouple to avoid
ambient
temperatures
from
influencing
reading.
Temperature
measured
by thermocouple
and temperature
determined
from
thermistor voltage reading should be close, within 5°F, if care was
taken in applying thermocouple and taking readings.
If a more accurate check is required, unit must be shut down and
thermistor removed and checked at a known temperature (freezing
point or boiling point of water) using either voltage drop measured
across thermistor
at the J8 terminal, or by determining
the
resistance with unit shut down and thermistor
disconnected from
J8. Compare the values determined with the value read by the
control in the Temperatures mode using the Scrolling Marquee
display.
37