Outdoor Fan Operation; Economizer Operation - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Outdoor
Fan Operation
The 48/50 PD units use a multi-speed
outdoor
fan motor to control
the
head
pressure
within
an acceptable
range
at low
outdoor
ambient
temperatures.
On the 48 and 50 PD-05
and 06 size units
the outdoor
fan contactor
is powered
on the
load
side of the
compressor
contactor
so the outdoor
fans will run only
when the
compressor
contactor
is
energized.
When
the
outdoor
fan
contactor
is not energized
the
outdoor
fan runs
at high
speed.
When
the outdoor
fan contactor
is energized
the outdoor
fan runs
at low speed.
The outdoor
fan speed is controlled
by a system
three of fan levels
set up in the control
software.
Table 6 shows
the three levels and
fan
speeds
for each
level.
The
fan levels
are deternfined
by
Outdoor
Air Temperature
(Temperatures-,AIR.T-,OAT)
but can
be
overridden
by
Condenser
Pressure
A
(Pressures-+SCP,4)
inputs
to the Main Base Board.
FAN
LEVEL
FAN
SPEED
OFF
LOW
HIGH
CONDITIONS
TO TRANSITION
TO NEXT
LOWER LEVEL
N/A
1. Compressor
Contactor is OFF
1. Outside Air Temperature
Control
--
Fan
Lev2 Off Temperature
45 F or below (Confi-
guration--,COOL--,OFC--,2.OFF
< =45F)*
2. Condenser
Pressure A Override
--
Fan
Lev2 Min Pressure
200 psig or below (Config-
uration--,COOL--,OFC--,2.MNP<
= 200 psig)*
CONDITIONS
TO TRANSITION
TO NEXT
HIGHER LEVEL
1. Compressor
Contactor
is ON
(on initial start up outdoor fan runs at Level 2 for
10 seconds before moving to correct level based
on outside air temperature or Condenser
Pres-
sure A)
1. Outside Air Temperature
Control -- Fan
Lev2 On Temperature
55 F or above (Configu-
ration--,COO L--,O FC--,2.ON > =55F)*
2. Condenser
Pressure A Override -- Fan
Levl Max Pressure
450 psig or above (Config-
uration--,COOL--,OFC--,1
.MXP> = 450 psig)*
N/A
Table 6 -- Fan Level Control
of Outdoor
Fan
*Configuration
parameters
1.MXE
2.MNE
2.ON
and 2.OFF
factory
default
configuration
should
not be changed.
The default
configurations
have
been
qualified
over
a wide
range
of conditions
and are provided
in case
a field
replacement
of the control
board
occurs
and the settings
need
to be checked
or manually
configured.\
Economizer
Operation
If
an
econonfizer
is
installed,
then
Econonfizer
Installed
(Configuration--_UNIT--_EC.EN)
should
be
set to
YES.
The
economizer
is controlled
by
the
Econo
Commanded
Position
(Outputs-,ECON-,EC.CP)
on the
Economizer
Control
Board
(ECB).
Feed
back
from
the
econonfizer
actuator
is output
on
configuration
parameter
Econo
Actual
Position
(Outputs-+
E CON-+ E C _4P) .
Economizer
Actuator
Communication
The
econonfizer
actuator
used
with
the
48/50PD
units
is a
Multi-Function
Technology
(MFT)
actuator.
This
allows
the
ComfortLink
system
to communicate
with
the actuator
through
a
feedback
signal.
The
configuration
Econonfizer
Control
Type
(Configuration-+ECON-+E.CTL)
deternfines
the conmmnication
method,
either digital or analog,
used to communicate
between
the
Economizer
Control
Board and the economizer
actuator.
The power
to the unit must be cycled
after the Economizer
Control
Type (Configuration
--+ECON--+E.CTL)
configuration
parameter
is changed.
E.CTL
= 1 or 2 (Digital/Position
or Digital/Command)
When
Econonfizer
Control
Type
(Configuration-+ECON-+E.CTL)
is set to 1, the
Econonfizer
Control
Board
will
communicate
with
the economizer
actuator
using
the digital
protocol,
from
Econonfizer
Control
Board
plug
J7-1 to actuator
pin 5. The commanded
position
and the actuators
actual
position
are communicated
back
and
forth
between
the
actuator
and the Economizer
Control
Board.
When the Economizer
Control
Board
and actuator
first initiate
communication,
a Control
Angle
Econonfizer
Control
Type
(Operating
Modes'---,
ECON--+C_4NG)
is provided
to the Econonfizer
Control
Board
and defines
the actuator's
range of motion.
The control
angle must
be
greater
than
the
Min
Actuator
Ctrl
Angle
(Configuration-+ECON-+M_4NG).
During
this
digital
control,
the Economizer
Control
Board
analog
4 to 20 mA output
will
represent
the
actuator's
actual
position
when
E.CTL
= 1 or
commanded
position
when
E.CTL
= 2. Because
the wiring
has a
built-in
500-ohm
resistor,
the 4 to 20mA
signal is converted
to a 2
to 10VDC
signal
that is accessible
via a field connected
ternfinal
board
TB-8
and TB-9.
However,
before this signal can be read
remotely,
the
violet
wire
that
connects
the
actuator
to
field
connection
ternfinal board
TB-J10-8
must be removed
or cut.
E.CTL
= 3 (Analog
Control)
When E.CTL
is set to 3, the Econonfizer
Control
Board
will NOT
conmmnicate
with
the economizer
actuator
directly
with
the 4 to
20mA
analog
signal
wired
to TB-8
and
TB-9
along
with
the
500-ohm
resistor
producing
a 2 to 10VDC
signal for the actuator.
While
in this mode,
the actuator's
built-in
2 to 10VDC
feedback
signal s accessible
via TB-9
and TB-10
any time because
it is not
used by the Econonfizer
Control
Board.
Free
Cooling
The
econonfizer
will
be
allowed
to help
with
cooling
if the
Outdoor
Air Temperature
(Temperatures--,AIR.T--,OAT)
is less
than
the
configured
Econo
Cool
Hi
Temp
Linfit
(Configuration-+ECON-+EH.LO)
and
greater
than
the
configured
Econo
Cool
Lo
Temp
Linfit
(Configuration-+ECON-+EL.LO).
If
an
enthalpy
sensor
is
installed,
the outdoor
temperature
must be below
the Econo
Cool
Hi
Temp
Linfit
(Configuration--+ECON--+EHJ_O)
and
the
Outdoor
Enthalpy
Switch
(Inputs-+GENd-+ENTH)
must
be
LOW.
Unoccupied
Free Cooling
The unoccupied
free cooling
algorithm
attempts
to maintain
the
building
space
half way
between
the Occupied
Cool
Set Point
(Setpoints-,OCSP)
and
Occupied
Heat
Set
Point
(Setpoints-,OHSP)
using
only
the
econonfizer
when
the
conditions
in the building
and the outdoors
are suitable.,
during
UNoccupied
periods
if the air in the building
and the outdoor
air
are suitable.
Three different
configurations
define this algorithm:
1. Unoccupied
Free
Cooling
(Configuration-+ECON-+