Indoor Air Quality (Iaq) - Carrier 48/50PD05 User Manual

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron(r--410a)refrigerant and comfortlink 1.x controls
Table of Contents

Advertisement

a. (Configuration→ECON→UEFC = 0) - - Disabled
When UEFC = 0, unoccupied free cooling is disabled.
Cooling will only occur if the space exceeds the
unoccupied setpoints.
b. (Configuration→ECON→UEFC = 1) - - Unoccupied
When UEFC is set to 1, unoccupied free cooling can
occur throughout the entire unoccupied period. The
space temperature must be higher then the mid- -point
between the occupied cooling and heating set points.
c. (Configuration→ECON→UEFC = 2) - - Preoccupancy
When UEFC is set to 2, unoccupied free cooling can
only occur when the time until the next occupied period
is less than the Free Cool PreOcc Time (FC.TM) in
minutes.
2. Free
Cool
(Configuration→ECON→FC.TM)
FC.TM is the configuration that determines how many
minutes before occupancy that free cooling can occur when
set for Preoccupancy (UEFC = 2).
3. 1.Free
Cool
(Configuration→ECON→FC.LO)
Unoccupied free cooling cannot occur if the Outdoor Air
Temperature (Temperature→ AIR.T→ OAT) is less than
FC.LO.
Power Exhaust
To
enable
power exhaust
(Configuration→ECON→PE.EN) to YES. On the 48/50PD- -05
and 06 size units both power exhaust fans are wired together and
are controlled by the configuration Power Exhaust Stage1 CFM
(Configuration→ECON→PE1.C). When the Indoor Fan Max
Speed CFM (Configuration→ECON→IDF.C) is set to the correct
supply duct CFM (either by fan tables or air balance report) the
control will calculate the outside air CFM based on outside air
damper
position
and
(Outputs→FANS→F.SPD) to turn on the power exhaust when the
calculated outside air CFM reaches Power Exhaust Stage1 CFM
(Configuration→ECON→PE1.C). The power exhaust will turn
off when the calculated outside air CFM falls below Power
Exhaust Stage1 CFM (Configuration→ECON→PE1.C).
Power Exhaust Stage2 CFM (Configuration→ECON→PE2.C) is
not currently used on the 48/50PD- -05 and 06 units.

Indoor Air Quality (IAQ)

The ComfortLink TM control has the capability for several
methods of demand ventilation control.
typically measured using a CO2 sensor whose measurements are
displayed in parts per million (ppm). Outdoor air quality may be
measured with a CO2 sensor for indoor- -outdoor differential
demand ventilation control, or with other sensor types for the
outdoor air lockout function. The factory- -installed indoor air
quality CO2 sensor is mounted in the return section.
field- -installed indoor air quality CO2 sensor may be mounted in
the return or directly in the occupied space, per job requirements.
The indoor air quality modes of operation can be affected by the
IAQ Analog Input Config (Configuration→ AIR.Q→ IA.CF),
IAQ Switch Input Config (Configuration→ AIR.Q→ IA.CF),
OAQ Analog Input Config (Configuration→ AIR.Q→ OA.CF)
and other related fan and limit configurations as described below.
IAQ (Analog Input)
The ComfortLink TM control is configured for indoor air quality
sensors which provide 4 to 20 mA signal for 0 to 2000 ppm CO2.
If the sensor being used has a different range, the ppm display
range must be reconfigured by entering new values for the IAQ
Sensor Value at 4mA (Configuration→AIR.Q→I.4M) and IAQ
Sensor Value at 20mA (Configuration→AIR.Q→I.20M).
IA.CF = 0 (No IAQ)
IA.CF = 0 signifies that there is no IAQ sensor installed. The
damper will operate at the Econ Min at Max Fan Speed
PreOcc
Time
Low
Temp
Limit
set Power
Exhaust Installed
Commanded
Fan
Speed
The
Indoor air quality is
A
(Configuration→ECON→MP.MX) when the fan is at Supply Fan
Maximum Speed (Configuration→UNIT→FS.MX) and the
damper position will vary at other fan speeds as described in the
Cooling Mode with Economizer section below when the space is
occupied and the indoor fan is on.
IA.CF = 1 (DCV)
When IA.CF = 1 the IAQ algorithm is set for Demand Control
Ventilation (DCV). During DCV, the damper modulates between
two user configurations depending upon the relationship between
the Indoor Air Quality (IAQ) and the Outdoor Air Quality (OAQ).
The lower of these two positions is referred to as the Econo Min
IAQ Position (Configuration→AIR.Q→AQ.MN) while the higher
is referred to as the Econ Min at Max Fan Speed
(Configuration→ECON→MP.MX).
Position (Configuration→AIR.Q→AQ.MN) should be set to an
economizer position that brings in enough fresh air to remove
contaminates and CO2 generated by sources other than people.
The
Econ
Min
(Configuration→ECON→MP.MX)
economizer position that brings in fresh air to remove contaminates
and CO2 generated by all sources including people when the
indoor fan is operating at the Supply Fan Maximum Speed
(Configuration→UNIT→FS.MX). The Econ Min at Max Fan
Speed (Configuration→ECON→MP.MX) value is the design
value for maximum occupancy.
The ComfortLink TM control will begin to open the damper from
the Econo Min IAQ Position (Configuration→AIR.Q→AQ.MN)
position when the IAQ level begins to exceed the Outdoor Air
Quality (OAQ) level by a configurable amount. This amount is
referred
to
as
(Configuration→AIR.Q→AQD.L).
between IAQ and OAQ reaches AQ
(Configuration→AIR.Q→AQD.H), the economizer position will
be
at
the
Econ
Min
(Configuration→ECON→MP.MX) when the indoor fan speed is
at
Supply
Fan
(Configuration→UNIT→FS.MX).
differential
is
between
(Configuration→AIR.Q→AQD.L) and AQ Differential High
(Configuration→AIR.Q→AQD.H), the control will modulate the
damper
between
Econ
(Configuration→ECON→MP.MX) and Econo Min IAQ Position
(Configuration→AIR.Q→AQ.MN) in a linear manner as shown
in Figure 3. At other fan speeds the economizer damper will
operate in the shaded area between the two economizer position
curves but at the actual fan speed as indicated by Commanded Fan
Speed (Outputs→FANS→F.SPD).
IA.CF = 2 (Override IAQ)
When IA.CF = 2, the IAQ algorithm maintains the damper at Econ
Min at Max Fan Speed (Configuration→ECON→MP.MX) when
the indoor fan speed is at Supply Fan Maximum Speed
(Configuration→UNIT→FS.MX) or in the shaded area of Figure
3 when the indoor fan speed is at the Commanded Fan Speed
(Outputs→FANS→F.SPD) until the override condition triggers.
The override triggers when the IAQ/OAQ differential is greater
than AQ Differential High (Configuration→AIR.Q→AQD.H).
The IAQ Override Position (Configuration→AIR.Q→OVR.P).
The economizer damper will return to the Econ Min at Max Fan
Speed (Configuration→ECON→MP.MX) or MP.MX curve at
other fan speeds when the IAQ/OAQ differential is less than the
AQ Differential Low (Configuration→AIR.Q→AQD.L).
The override algorithm will operate whenever the building is
occupied and the indoor fan is operating or whenever the IAQ
algorithm has caused the indoor fan to operate. The IAQ Analog
Fan Config (Configuration→AIR.Q→IA.FN) determines whether
or not the IAQ algorithm can turn on the indoor fan.
If the indoor fan is not operating, the economizer position will be
zero. If the override is not active and the building is unoccupied,
the economizer position will be zero. The damper position may
16
The Econo Min IAQ
at
Max
Fan
Speed
should
be
set
to
AQ
Differential
Low
When
the
differential
Differential High
at
Max
Fan
Speed
Maximum
Speed
When
the
IAQ/OAQ
AQ
Differential
Low
Min
at
Max
Fan
Speed
an