First alarm: 010-01
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
** Heavy Smoke **
Zone 002 Address 03
SMOKE
YYYY-MM-DD hh:mm
User definable alarm text
(if programmed.)
Heavy smoke / heat alarm will be reset when the fire alarm
respectively is reset, see chapter "Alarm reset", page 53.

Alert Annunciation alarm (AA alarm)

When the AA function is enabled, indicated by the LED Routing
equipment "Fire brigade tx delay" (L14), the indications, print-outs,
actions etc. are the same as for a normal fire alarm (see above) except
for the c.i.e. output for routing equipment (fire brigade tx), which
will not be activated directly. There will also be a "title", i.e. "Alert
annunciation" or "Alert annunciation acknowledged" will be added to
the normal fire alarm information.
acknowledged within an acknowledge time and reset within an
investigation time, otherwise the output(s) for routing equipment (fire
brigade tx) will be activated. See EBL512 G3 Planning Instructions
for more information regarding the AA function. Acknowledgement
and reset of the AA alarm can be done on an AA unit 1735 / 1736 or
an AA controller 1740. See also chapter "Alert Annunciation", page
54.
Alert annunciation
Zone
010-01
User definable alarm text for 010-01.
Menu
NOTE! The "Ackn. alert annunciation" text is only visible if an AA
alarm is activated and not if this key is used for the "Evacuate"
function.
47
The AA alarm has to be
Alarm number 1 (of 1)
Address
SMOKE
Ackn. alert
annunciation