Panasonic MEW01777 Operating Instructions Manual page 45

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
Rev: -
First alarm: 002-03
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
Normally all fire alarms will be presented in all control units (default)
but it is possible to have Selective alarm presentation, i.e. only fire
alarms from selected control units will be presented in the control unit
respectively. Set in EBLWin for each control unit.
See also chapter "The information area priority order", page 24. In
accordance with the EN54-2 standard, the following happens in case
of a fire alarm:
 The buzzer in the c.i.e. sounds 0.4 sec. each 0.4
0.4 sec.).
 LEDs "Fire" (L1) are blinking (0.4 / 0.4 sec.).
 Output for routing equipment (Fire brigade tx) and outputs
type "Routing equipment" are activated.
 Outputs for fire alarm are activated.
 In the c.i.e. display, a presentation number (zone/address) is
shown (for the first fire alarm).
 In the c.i.e. display, a user definable text message (alarm
text) is shown (if programmed).
 In the c.i.e. display, is also some additional information
presented.
One alarm point activating fire alarm.
Example; fire alarm zone 002, address 03 (within zone 002):
Zone
002-03
User definable alarm text for 002-03.
Menu
After the presentation number is automatically added
HEAT, MULTI or MCP depending on type of alarm point.
19
In case of Selective alarm presentation only for the selected alarms.
20
Outputs programmed for General fire alarm and outputs programmed for
the activated fire alarm(s).
43
th
sec. (0.4 /
19
20
Alarm number 1 (of 1)
Address
SMOKE
1 zone in alarm
SMOKE,