Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Output (H2/B2)

All programmable outputs in the c.i.e. and outputs in units connected
to the COM loops (except outputs of type "Alarm device") can be
individually disabled.
If you try to disable an output of type "Alarm device" it will be treated
as if it does not exist, see below.
Disabled output: Even if its control expression (trigger condition) is
fulfilled (true), the output will not be activated.
Text in display
H2 Disable or re-enable
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
Escape
menu
B2 Output
Disable output
Loop unit 000000 output 0
Change type of
disablements
98
Comments
According to chapter
"Access", see page 88.
Via menu B2 can a loop
unit output, C.U. output
S0-S3 / R0-R1 and exp.
board output be
disabled.
Use the soft key "
Change
" to
type of disablements
toggle between:
Loop unit output
Control unit output S
Control unit output R
Exp. board output
Write loop unit technical
number and output
number and press "
"
to disable, which will be
indicated with "√" and a
beep. The output will
directly be shown in the
Re-enable list