In an "unstable" environment the Performance factor will be higher than 0.00.
This could for example be the case in a factory (e.g. "dirty" activities during
working hours – no or clean activities during the night) and is not a problem
as long as there are no nuisance (false) alarms or other problems.
Algorithms
Table showing the algorithms and the shortenings respectively:
Detectors 3308/3309, 430x and 440x, all in NORMAL mode.
Normal sensitivity (3%/m) & Normal detection (15 s)
High sensitivity (2.4%/m) & Normal detection (15 s)
Low sensitivity (3.6%/m) & Normal detection (15 s)
Normal sensitivity (3%/m) & Slow detection (35 s)
High sensitivity (2.4%/m) & Slow detection (35 s)
Low sensitivity (3.6%/m) & Slow detection (35 s)
Heat algorithm, Class A1
Heat algorithm, Class A2 (S)
Heat algorithm, Class B (S)
Decision algorithm
Default is N-15 and A1 respectively.
Algorithm
Detector 4400 / 4401 in Advanced mode.
Normal area
Clean area
Smoke-Steam area
Cooking-Welding area (Not valid for 4401)
Heater area
Default is Normal.
48
If some other short name is wanted, it can be changed in EBLWin. Up to
six characters can be used.
49
Analog multi detector 4300 only.
114
Algorithm
(Not valid for 4401)
Short
48
name
N-15
H-15
L-15
N-35
H-35
L-35
A1
A2
B
49
Dec
Short name
Normal
Clean
Smoke
Welding
Heater