Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Fault

All faults are delayed in order not to generate any unnecessarily faults,
e.g. for COM loop and zone line input faults the delay time is approx.
25
45 seconds.
In case of a fault condition, the following will happen in the control
unit:
 The buzzer in the c.i.e. will sound continuously (steady).
 The fault condition output for routing equipment (Fault tx)
will be activated.
 Programmable output(s) for general fault will be activated
and output(s) for general charge fault might be activated.
 LED Routing equipment "Fault tx activated" (L13) will be
turned on (indicating that the fault condition output for
routing equipment (Fault tx) is activated).
 LED Fault / Disablements "General fault" (L9) will be
turned on.
 LEDs Fault / Disablements "Alarm devices" (L11),
"System fault" (L7) and/or Fault / Disablements "Fire
brigade tx" (L12) might be turned on as well.
 A fault message incl. date, time and status will be shown in
the c.i.e. display. If it is an alarm point or zone also the User
definable alarm text will be shown.
Example; fault message:
FAULT: No reply zone: xxx address: xx
technical number xxxxxx
User definable alarm text
yyyy-mm-dd hh:mm
Number of not ackn. faults in system: 1
Menu
NOTE!
When the Russian, Ukraine, Australian or the New Zealand language
is selected the date is shown as follows: dd-mm-yyyy.
25
Some units may also have an internal delay time, which makes the delay
time even longer, e.g. the Multipurpose I/O unit 3361 has an internal delay
time of 30 seconds, which results in 45+30=75 seconds delay time in total.
26
The buzzer in the control unit can be suppressed for faults generated in
other control units. "Suppressed buzzer during fault" is set via EBLWin.