Local Alarm Acknowledgement (Laa); Quiet Alarm - Panasonic MEW01777 Operating Instructions Manual

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
Rev: -
16.8
16.9
Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Local Alarm Acknowledgement (LAA)

One or more Local Alarm Acknowledgement Units are used in the
system.
See EBL512 G3 Planning Instructions chapter "Local Alarm
Acknowledgement (LAA)" for more information regarding the LAA
function.
During the Acknowledgement Period (10-120 sec.), the following
information (a list if many) is shown in the c.i.e. display:
LAA zone zz, activated
dd-mm-yyyy hh:mm
During the Investigation Period (1-9 min.), the following information
(a list if many) is shown in the c.i.e. display:
LAA zone zz, investigation in progress
dd-mm-yyyy hh:mm

Quiet alarm

One or more smoke detectors, via EBLWin programmed for Quiet
alarm, have passed the fire alarm level. Quiet alarm is used for fan
control (stop or start is depending on the type of fan).
Quiet alarm is normally used in conjunction with one I/O Matrix
board 4582, one application board for fan control
for fan control 3361, for control of each fan.
Indications and actions:
Detector LEDs are turned on (i.e. also a connected ext. LED).
LEDs "Fire" (L1) are blinking (0.4 / 0.4 sec.), the buzzer sounds (0.8 /
5 sec.) and there is a Quiet alarm presentation (incl. a title "Quiet
alarm") in the display:
24
The Fan control panel 4593 can be used for control of up to eight fans.
51
Quiet alarm
24
and one I/O unit