Operating Instructions Fire alarm system EBL512 G3, V2.2.x
During the "restart", no fire alarm can be activated and the following
is shown in the display:
Panasonic
And after a few seconds (if everything is all right, else see Memory
fault below):
A fault will be generated and the following text message will be
shown in the display and the buzzer will sound:
FAULT: Restart control unit nn, code xx,
address yyyyyy
Regarding code xx and address yyyyyy, see page 71. This fault is also
indicated by LEDs Routing equipment "Fault tx activated" (L13) and
Fault / Disablements "General fault" (L9).
After the fault is acknowledged (via menu H6), the LEDs will be
turned OFF if there are no other faults.
After any restart, required individual disablements have to be done.
Memory fault
In case of a fault in the Main board 5010 S/W (system program) or the
MMI board 5011 S/W, the following fault message might be shown:
FAULT: Checksum system program, control unit xx
(Main board software.)
FAULT: Checksum MMI program, control unit xx
(MMI board software.)
FAULT: No connection with MMI board, control unit xx
(Not shown in the display, only via EBLWin, the Web-server or via
another unit in the system.)
No contact with Main board
This is also indicated by LED "System fault" (L7) and the buzzer
sounds steady (continuous). The Fault tx output is "activated".
86