Operating Instructions
MEW01777
Revision -
Fire Alarm System EBL512 G3
V2.2.x
Author:
Jan Pettersson
Date of issue: 2015-01-19
Date of rev:

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic MEW01777

  • Page 1 Operating Instructions MEW01777 Revision - Fire Alarm System EBL512 G3 V2.2.x Author: Jan Pettersson Date of issue: 2015-01-19 Date of rev:...
  • Page 2 This page has deliberately been left blank.
  • Page 3: Table Of Contents

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Table of contents Introduction________________________________ 7 Definitions / Explanations ____________________ 9 PESN AB ________________________________________ 9 Alarm points ______________________________________ 9 2.2.1 Smoke detector ________________________________ 9 2.2.2 Sensor _______________________________________ 9 2.2.3...
  • Page 4 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 3.5.3 Web-server configuration _______________________ 15 Control Unit ______________________________ 16 LED indicators and push buttons _____________ 18 The display (LCD) _________________________ 22 Areas in the display ________________________________ 22...
  • Page 5 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 16.6 Co-incidence alarm (2-address / -zone dependence) _______ 49 16.7 Delayed alarm ____________________________________ 49 16.8 Local Alarm Acknowledgement (LAA) ________________ 51 16.9 Quiet alarm ______________________________________ 51 Alarm reset _______________________________ 53 17.1...
  • Page 6 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 26.2 Disablement by time channel (H4/U2) ________________ 110 26.3 Open doors (H4/U3) ______________________________ 111 26.4 Sensor values (H4/U4) ____________________________ 112 26.5 Sensors activating SERVICE signal (H4/U5) ___________ 115 26.6...
  • Page 7 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x...
  • Page 8 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x...
  • Page 9: Introduction

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Introduction EBL512 G3 Operating Instructions is a document intended to be used by the end-user and the fire brigade personnel as well as service / commissioning engineers.
  • Page 10 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x  sometimes additional information, such as Convention (different functions / facilities), Language, Number of addresses, etc. PC S/W A PC S/W is a program used for programming, commissioning, etc. It...
  • Page 11: Definitions / Explanations

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Definitions / Explanations Definitions / explanations / abbreviations / etc. frequently used or not explained elsewhere in the document. PESN AB Panasonic Eco Solutions Nordic AB Alarm points Units, which can generate a fire alarm (in the control unit), i.e.
  • Page 12: Output Unit

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 2.2.8 Conventional zone line input / External line Input intended for one or more conventional alarm points. End-of-line device in the last alarm point.
  • Page 13: System / Installation

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 2.11 System / Installation One control unit or several control units connected via a TLON network (co-operating control units). ® ® 2.12 Network / TLON...
  • Page 14: Site Specific Data (Ssd)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x switch is replaced with a key switch. An open door is indicated in the LCD (i.e. an "open door" icon). 2.17 Site Specific Data (SSD) The SSD is unique for each installation.
  • Page 15: Overview

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Overview The EBL512 G3 system EBL512 G3 is a microprocessor controlled intelligent fire alarm system, intended for analog addressable smoke detectors, as well as conventional detectors and manual call points.
  • Page 16: Software (S/W) Versions

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x The second power source is a backup battery (2 x 12 V). In the c.i.e. is space for two 27 Ah batteries. Larger batteries (up to 65 Ah) have to be placed outside the c.i.e.
  • Page 17: Tlon Manager

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x  create and download / make a backup (upload) of site specific data (SSD).  download new software / settings / convention / configurations / control unit &...
  • Page 18: Control Unit

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Control Unit Figure 1. Left: The EBL512 G3 Control Unit 5000, with printer. The look might vary according to configuration, country, etc. Right: The EBL512 G3 Control Unit 5001.
  • Page 19 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x P4 – P7 L7, L8 L9, L10 L11, L12 L13, L14 Figure 2. The EBL512 G3 front with display; The Fire Brigade Panel (FBP) is the upper part and the Control Panel (CP) is the lower part.
  • Page 20: Led Indicators And Push Buttons

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x LED indicators and push buttons LEDs and push buttons can vary according to type and configuration (convention / country / language). See also Figure 2, page 17.
  • Page 21 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Push buttons on the Fire Brigade Panel (FBP) Push button Operation/function Silence buzzer (yellow) Used to silence the buzzer in the c.i.e. when it is sounding.
  • Page 22 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x LED indicators on the Control Panel (CP) LED indicator Indicating System fault (yellow) EBL512 G3 is not running because of S/W, CPU or memory fault, no contact between main board and MMI board or c.i.e.
  • Page 23 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Push buttons / Keypad on the Control Panel (CP) Key/push button Operation/function ↵ (Enter) Used to log on, i.e. to get access to the menu tree (via an access code) and to accept a menu and accept input of data.
  • Page 24: The Display (Lcd)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x The display (LCD) Areas in the display Symbol area Information area Soft key area Menu Next zone Re-enable Evacuate  Symbol area: Some events are indicated with symbols, see 6.2 below.
  • Page 25: The Symbol Area

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x The symbol area The symbol area is at the top of the display, see chapter 6.1. The following table explains the meaning of each symbol:...
  • Page 26: The Information Area Priority Order

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x The information area priority order When the control unit / system is in normal operation (quiescent state), i.e. no fire alarms, no faults, no disablements, no service...
  • Page 27: System Information In The Lcd

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x System information in the LCD EBL512 G3, control unit number, date and time are displayed. The exact look is convention / language dependent. One example of the information area:...
  • Page 28: User Level, User Name & Password

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x User level, User name & Password EBL512 G3 has different user levels for different kind of users. To log on to an EBL512 G3 (version > 2.0) a User name and a Password are required.
  • Page 29: User Level 1

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x It is highly recommended to change the default user names and passwords and to add a number of new user names and passwords. Also the EBL and WEB columns have to be filled in, depending on how the user names and passwords shall be used.
  • Page 30: User Level 2B

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x User level 2B After the door has been opened with the fire brigade key ("Door open" symbol in the symbol area), you have access to level 2A and after log on as “Information only”...
  • Page 31: User Level 2C

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x User level 2C After the door has been opened with the fire brigade key ("Door open" symbol in the symbol area), you have access to level 2A and after log on as “Building officer”...
  • Page 32: User Level 3A

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x User level 3A After the door has been opened with the fire brigade key ("Door open" symbol in the symbol area), the service / maintenance personnel have access to level 2A and after log on as “Service personnel”...
  • Page 33: Passwords / Change Of Password

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x configurations, on-line status checking, etc. An EBLWin key (5094) is required to be plugged in the PC. Passwords / Change of password Normally the user names and passwords are downloaded / changed via EBLWin (menu System | User data), i.e.
  • Page 34: "Silence Alarm Devices

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x "Silence Alarm devices" In the control unit front (the FBP part) there is a push button "Silence alarm devices" (P2). When the alarm devices are activated (sounding) and the push button "Silence alarm devices"...
  • Page 35: Disable Or Re-Enable Alarm Devices

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Disable or Re-enable alarm devices Outputs programmed for sounders (i.e. type "Alarm devices") can via menu H2/B4 be collectively disabled for all control units. This is indicated by LED Fault / Disablements "General disablements"...
  • Page 36: 10 "Silence Buzzer

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x "Silence buzzer" The buzzer in the control unit will sound for:  Fire alarm (0.4 / 0.4 sec.)  Co-incidence alarm (2-zone or 2-unit dependent fire alarm): When only one zone or one zone / address (alarm point) is in alarm status (0.8 / 5 sec.)
  • Page 37: Disable Or Re-Enable Output

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Disable or re-enable Output All control outputs (except outputs of type “Alarm devices”) can via menu H2/B2, be individually disabled:  Loop unit xxxxxx output x ...
  • Page 38: Disable Or Re-Enable Control, Ventilation, Extinguishing And Interlocking Outputs

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Disable or re-enable Control, Ventilation, Extinguishing and Interlocking outputs All control outputs programmed as type:  Control (general)  Ventilation (Fire ventilation)  Extinguishing ...
  • Page 39: Evacuate

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Evacuate When the soft key "Evacuate" (P7) is pressed , all outputs programmed for sounders (i.e. type "Alarm devices"), will be collectively turned ON (steady). This is indicated in the LCD:...
  • Page 40: Open Door

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Open door A special key is used to open the control unit door to get access to the front / system. The same type of key is also used to open the ext. FBP door.
  • Page 41: Technical Number / Presentation Number

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Technical number / Presentation number 15.1 Technical number for COM loop units The technical number, NNNNNN, is used when programming all units connected to the COM loops.
  • Page 42: Presentation Number

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 15.2 Presentation number For each fire alarm point / input / zone, a presentation number, NNN-NN, has to be programmed. The presentation number is shown in the c.i.e.
  • Page 43: Alarm Types

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Alarm types In case of a fire, analog detectors (sensors), conventional smoke and/or heat detectors, manual call points and programmable inputs can activate fire alarm. If somebody illegally breaks into a key cabinet, this will also activate a "fire alarm"...
  • Page 44: Fire Alarm

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x  The buzzer in the c.i.e. sounds 0.8 sec. each 5 sec. (0.8 / 5 sec.).  Outputs programmed for pre-warning are activated.  In the c.i.e. display, a presentation number (zone/address) is shown (for the first pre-warning).
  • Page 45 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Normally all fire alarms will be presented in all control units (default) but it is possible to have Selective alarm presentation, i.e. only fire alarms from selected control units will be presented in the control unit respectively.
  • Page 46 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x More than one alarm point activating fire alarm. Example; fire alarm in zone 002, address 03 (within zone 002) and nine other fire alarms (of which the latest alarm is 003-11) in four...
  • Page 47: Entering The Menus During Fire Alarm

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x ** Fire Alarm ** Zone 002 Address 03 SMOKE YYYY-MM-DD hh:mm User definable alarm text (if programmed) Reset of the fire alarms, see chapter "Alarm reset", page 53.
  • Page 48: Heavy Smoke Alarm / Heavy Heat Alarm

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x added. If a printer is available the test mode alarm will be printed with the information "(test mode)" added. No outputs will be activated except the fire door outputs. The test mode alarm will be automatically reset after approx.
  • Page 49: Alert Annunciation Alarm (Aa Alarm)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x ** Heavy Smoke ** Zone 002 Address 03 SMOKE YYYY-MM-DD hh:mm User definable alarm text (if programmed.) Heavy smoke / heat alarm will be reset when the fire alarm respectively is reset, see chapter "Alarm reset", page 53.
  • Page 50: Key Cabinet Alarm

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 16.5 Key cabinet alarm The fire brigade uses a key cabinet to store a key to the building. One programmable input per c.i.e. can be used to connect a key cabinet.
  • Page 51: Co-Incidence Alarm (2-Address / -Zone Dependence)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 16.5.2.1 Restoring the key after a fire alarm When all fire alarms in the system are reset (see chapter "Alarm reset", page 53), the key has to be restored into the key cabinet within 5 minutes.
  • Page 52 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x The delay time (0-255 sec.) is, for the whole system, set via EBLWin (System Properties, page 1). The delay time will be added at the end of the alarm algorithm when a fire alarm normally would have been activated.
  • Page 53: Local Alarm Acknowledgement (Laa)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 16.8 Local Alarm Acknowledgement (LAA) One or more Local Alarm Acknowledgement Units are used in the system. See EBL512 G3 Planning Instructions chapter "Local Alarm Acknowledgement (LAA)"...
  • Page 54 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Zone Address 123-45 SMOKE User definable alarm text for 123-45. Menu Programmable outputs for quiet alarm, e.g. 3361 outputs controlling supply air fans and standard fans, i.e. any output with a control expression containing the trigger conditions "Quiet Alarm Zone"...
  • Page 55: Alarm Reset

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Alarm reset 17.1 Pre-warning reset Pre-warning is automatically reset. 17.2 Fire alarm reset NOTE! The detectors having activated fire alarm shall, after reset, be inspected, tested and replaced when required.
  • Page 56: Single With Automatic Disablement

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x When all fire alarms are reset, LEDs "Fire" (L1) and "Alarms queued" (L6) are turned off. If there are other conditions (e.g. a fault condition) the corresponding information will be shown (e.g.
  • Page 57: Key Cabinet Alarm Reset

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x button "Reset" on an AA unit 1735 / 1736 or an AA controller 1740 or in the c.i.e. NOTE! Reset via an AA unit is possible only during the investigation time and of AA alarm(s) only (not normal fire alarms).
  • Page 58: Quiet Alarm Reset

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 17.9 Quiet alarm reset Quiet alarms are non-latching, i.e. they will be automatically reset when the alarm point / zone is no longer above alarm level. Outputs activated by quiet alarm will be de-activated.
  • Page 59: Fault

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Fault All faults are delayed in order not to generate any unnecessarily faults, e.g. for COM loop and zone line input faults the delay time is approx.
  • Page 60 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x  In the c.i.e. display can up to three fault messages be shown simultaneously. In the display, down to the left, is displayed the number of not acknowledged faults.
  • Page 61: Fault Messages

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 18.1 Fault messages Below follows a list of all fault messages, in alphabetical order. There is also an explanation to each fault. Checksum fault in downloaded data.
  • Page 62 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x The Aspiration smoke detector Aspect Lazeer is not working as it should be, i.e. the unit has not been calibrated in conjunction with commissioning.
  • Page 63 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Valid for the wireless smoke detector 4611. The battery voltage is < 2.8 V. The batteries have to be replaced. FAULT: Charger, control unit xx The battery charging function is not OK.
  • Page 64 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x mixed Network 0 and Network 1 cables.)  Faulty TLON connection board 1590 / 5090.  The control unit has no power.  Can be shown in conjunction with new S/W download.
  • Page 65 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Voltage to earth > 18.3 V = Earth fault (plus). Check all cables (for damage, etc.). The function of the control unit cannot be guaranteed. Call for service personnel/engineer.
  • Page 66 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x control unit xx The fault is to be found in the extinguishing system, which has a fault output connected to a programmable supervised input in the EBL512 G3 system, in control unit no.
  • Page 67 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x another type in the SSD or a fault in the unit. FAULT: Fuse on COM-loop x, control unit xx Blown fuse F15 (Loop 0), F16 (Loop 1), F17 (Loop 2) or F14 (Loop 3) on the main board 5010, in control unit no.
  • Page 68 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x expansion boards (458x) in the control unit xx (EBL512 G3). FAULT: Key cabinet, control unit xx The key cabinet has been opened without a prior fire alarm (i.e. if somebody has opened the key cabinet illegally).
  • Page 69 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 700 mV.  The battery might be too old.  Cables, fuses etc. for externally placed batteries might cause a voltage drop.  Check / adjust the rectifier (power supply) voltage (24 V DC).
  • Page 70 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x FAULT: Mains, external power supply, control unit xx This is valid for external power supply equipment, which has a fault output connected to a programmable input in the EBL512 G3 system.
  • Page 71 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x personnel/engineer immediately. FAULT: No reply, expansion board x, control unit xx Valid for the 8 zones exp. board 4580, the 8 relays exp. board 4581 and the Inputs and outputs exp.
  • Page 72 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x The unit (e.g. a customized unit), cannot be found by the control unit.  Check the unit's COM loop address (with the programming tool 3314 / 4414).
  • Page 73 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x c.i.e. and vice versa. FAULT: Read/write site data (SSW), control unit xx SSW = the data that is changed during operation, i.e. week average sensor values, access codes, calibration values and event logs, in control unit no.
  • Page 74 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x xx, SCInn<->SCInn SCI nn <-> SCI nn describes between which Short Circuit Isolators the short-circuit is located. nn = A, B, 00, 01, 02, 03, 04, 05, 06, 07 - - 63. A & B is the built-in isolator in the EBL512 G3 c.i.e.
  • Page 75 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Ext. Fire Brigade Panel 1826 / 1828. There is no SSD (Site Specific Data) downloaded to the unit or something is wrong in the downloaded SSD.
  • Page 76 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x blinking. If the output is programmed for fire brigade tx (type Routing equipment), it is also indicated by LED Fault / Disablements "Fire brigade tx" (L12) blinking.
  • Page 77 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x TLON connection board 5090. No communication / connection with the TLON network. The board for Network 0 or 1 in control unit no. xx has to be replaced.
  • Page 78 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Check the type of unit, which should be the same as programmed via EBLWin. FAULT: Wrong type of unit zone: xxx address: xx and zone: yyy address: yy...
  • Page 79: Fault Acknowledge

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 18.2 Fault acknowledge The LEDs Routing equipment "Fault tx activated" (L13) and Fault / Disablements "General fault" (L9) are turned on (LEDs Fault / Disablements "Alarm devices" (L11), "System fault"...
  • Page 80 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x  Login, according to chapter "Access", page 88.  Use menu H6 (access level 2B) for fault acknowledge, see chapter "FAULT Acknowledge (H6)", page 132. Menu H6...
  • Page 81: Commissioning An Installation

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Commissioning an installation Before you connect the power supply to a control unit, all other cable connections shall be made. Check once more that they are correct.
  • Page 82: Control Units In A Tlon Network

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 19.2 Control Units in a TLON network The EBL512 G3 system can be build up as a single TLON Network or as a redundant TLON Network, i.e. two networks.
  • Page 83: Add A Control Unit In A Tlon Network

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x In a redundant network two Projects have to be created and installed. The Projects have to be identical but with different Project names. One project has to be installed for Network no. 0 and one has to be installed for Network no.
  • Page 84 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Open the current project in TLON Manager, delete the control unit according to the separate TLON network Operating Instructions MEW01361. Open the SSD for the current system via EBLWin. Delete the control...
  • Page 85: Upgrade Number Of Alarm Points

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Upgrade number of alarm points All EBL512 G3 settings are normally factory downloaded before delivery. It is however, on site possible to upgrade the maximum number of alarm points (128 ...
  • Page 86: Restart

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Restart A restart will delete or not delete the data in EBL512 G3. Below follows an explanation of the different data, abbreviations and a table showing how the data respectively is affected (cold or warm restart).
  • Page 87 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Action Data, etc. Data, etc. Restart which will be which will be code deleted not deleted Power down (de-energize) SSD, 00 (+50) then power up again.
  • Page 88 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x During the "restart", no fire alarm can be activated and the following is shown in the display: Panasonic And after a few seconds (if everything is all right, else see Memory fault below): Booting..
  • Page 89 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x A new download of the S/W (system programs) are required and/or the Main board and/or the MMI board have to be replaced. NOTE! After SSD download the following messages might be shown: Checksum fault in downloaded data.
  • Page 90: Access

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Access To use the key pad in the control unit (to get access to the menus), it is necessary to log in with a User name and a Password for level 2B, 2C or 3A.
  • Page 91 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x "2", If the password is correct a "Password" (six digits) main menu list is ▒▒▒ menu ↵ displayed. Press " " to H1 Perform monthly test...
  • Page 92 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Some lists are dynamic lists, i.e. the number of items per page depends on the size of each item. Some lists are static lists, i.e. a fixed maximum number of items per page.
  • Page 93: Perform Monthly Test (H1)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Perform monthly test (H1) The control unit and the installation shall be tested on a regular basis. If one twelfth of the alarm points are tested each month, the whole installation will be tested after one year.
  • Page 94 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x ↵ " " Zones in test mode: LED "Test mode" (L8) End test:  001 002 003 004 will light up. Perform the tests.
  • Page 95 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Monthly test is completed! ↵ Press ↵ ▒▒▒ menu " " Scroll to another menu or H1 Perform monthly test press " ". H2 ..
  • Page 96: Disable Or Re-Enable (H2)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Disable or re-enable (H2) A whole zone, one or more alarm points within a zone and/or control outputs can be disabled via menus H2/B1-B2. This function can be used for temporary disablement (e.g.
  • Page 97 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x NOTE! See chapter "The information area priority order", page 24, regarding priority order. Disablements (and faults) are indicated by a 2-sec. beep when you...
  • Page 98: Zone Or Zone/Address (H2/B1)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 24.1 Zone or Zone/Address (H2/B1) When a whole zone is disabled, all alarm points within the zone will be disabled except the addressable manual call points. (Not valid for the Australian and New Zealand conventions.)
  • Page 99 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Write the zone number Disable If the specified zone / √ and address Zone 003 address 01 unit doesn't exist, it will (e.g. 003, 01).
  • Page 100: Output (H2/B2)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 24.2 Output (H2/B2) All programmable outputs in the c.i.e. and outputs in units connected to the COM loops (except outputs of type "Alarm device") can be individually disabled.
  • Page 101 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Write loop unit Disable output If the specified output √ technical number and Loop unit 000000 output 0 doesn't exist, it will be output number, indicated with "X"...
  • Page 102: Output Type (H2/B3)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 24.3 Output type (H2/B3) All outputs of type "Control", "Ventilation", "Extinguishing" and Interlocking can be collectively disabled. Disabled output will stay in (or return to) the normal condition for the output respectively.
  • Page 103 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x ↲ " " Disable output type √ Control outputs in Control unit 00 -- Re-enable list (1) --------------------------------------------- All control outputs Use the soft key "|" to...
  • Page 104: Alarm Devices (H2/B4)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 24.4 Alarm devices (H2/B4) All outputs of type "Alarm device" can be collectively disabled. Disabled output will stay in (or return to) the normal condition for the output respectively.
  • Page 105 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x ↲ "|" Disable -------------------------------------------------------------- Press " " to re-enable. All alarm devices Re-enabled type will Re-enable list disappear from the list, All alarm devices indicated with a beep.
  • Page 106: Routing Equipment (H2/B5)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 24.5 Routing equipment (H2/B5) Disabled outputs are listed in menu H4/U1 from which it is possible to get a print-out. Outputs for routing equipment (fire brigade tx and fault tx) can be disabled and re-enabled via this menu.
  • Page 107 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x ↲ " " Disable routing equipment √ Fire Fault -- Disabled routing equipment --------------------------------- Fire alarm routing Use the soft key "|" to toggle between Disable and Disabled.
  • Page 108: Alert Annunciation (H2/B6)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 24.6 Alert Annunciation (H2/B6) Normal function: For alarm points / zones programmed for Alert Annunciation (via EBLWin) is normally the AA function enabled via a time channel, e.g.
  • Page 109 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x ↲ "|" Disable ------------------------------------ Press " " to re-enable. Alert annunciation Alert annunciation off Re-enable list will disappear from the Alert annunciation off list, indicated with a beep.
  • Page 110: Set Calendar And Clock (H3)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Set calendar and clock (H3) The RTC component has a capacitor as a backup power supply. Normally, date, day of the week and time only have to be set when the power is turned on the control unit for the first time.
  • Page 111: Present System Status (H4)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Present system status (H4) If a printer is mounted (an option for control unit 5000), it is possible to get a print-out from some of the menus. In this case, the soft key "Print"...
  • Page 112: Disablement By Time Channel (H4/U2)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 26.2 Disablement by time channel (H4/U2) A static list (up to four items per page) of all disablements by time channel(s) in the system.
  • Page 113: Open Doors (H4/U3)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 26.3 Open doors (H4/U3) If any door in the system is open the following symbol is shown in the display's symbol area: See also chapter "Open door", page 38.
  • Page 114: Sensor Values (H4/U4)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 26.4 Sensor values (H4/U4) The "Momentary" value in this menu will be updated after every detector polling, i.e. approx. every 6 second. The very first week average sensor value for the 430x and 440x detectors in NORMAL mode is calculated within 2½...
  • Page 115 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x ↲ " " If there are no sensors For an Analog multi detector 4300 / 4400 in NORMAL mode: (analog detectors) when Sensor: 001-01 (technical address 000001) ↲...
  • Page 116 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x In an "unstable" environment the Performance factor will be higher than 0.00. This could for example be the case in a factory (e.g. "dirty" activities during working hours –...
  • Page 117: Sensors Activating Service Signal (H4/U5)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 26.5 Sensors activating SERVICE signal (H4/U5) When SERVICE signal is generated in the system, following symbol is shown in the display's symbol area: Regarding the SERVICE signal levels, see Planning Instructions, chapter "SERVICE signal".
  • Page 118: Technical Warning (H4/U6)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 26.6 Technical warning (H4/U6) A technical warning is an event that is neither a fire alarm nor a fault. It is an information that something has or has not happened and is generated via a programmable input.
  • Page 119: Event Log (H4/U7)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 26.7 Event log (H4/U7) Three event logs (3 x 999 events) are available: 1. Alarm log (alarm events, e.g. fire alarm, fire alarm reset, etc.) 2.
  • Page 120: Information (H4/U8)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 26.8 Information (H4/U8) This menu can be used to show the following information for the specific control unit you currently use: Main board version The S/W (software / firmware / system program) version downloaded to the Main board 5010.
  • Page 121: Service (H5)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Service (H5) When commissioning an installation and by maintenance (e.g. when you power on and when you are programming a control unit / system), menu H5 can be used for certain actions, information and help.
  • Page 122: Calibration Of Supervised Outputs (H5/A1)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 27.1 Calibration of supervised outputs (H5/A1) Supervised (monitored) outputs The voltage outputs (S0-S3) in each control unit. The voltage outputs (VO0-VO1) in the COM loop output unit 3364.
  • Page 123: Sensitive Fault Detection Mode (H5/A2)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 27.2 Sensitive fault detection mode (H5/A2) To increase the possibilities to detect faults during the commissioning, it is possible to use the "Sensitive fault detection mode". The time delay for each fault will then be reduced, i.e.
  • Page 124: Service Mode For Com-Loop (H5/A3)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 27.3 Service mode for COM-loop (H5/A3) This mode can be used when commissioning an installation and by maintenance. The COM loop communication (polling) will be turned off but there is still voltage (24 V DC) on the loop in the A-direction only, in the B-direction only or in both directions at the same time.
  • Page 125 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x ↲ " " Service mode control unit 00 COM-loop 0 When you leave this menu ↲ " " Supplied from A-direction only by pressing "...
  • Page 126: Display Current Consumption In Unit (H5/A4)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 27.4 Display current consumption in unit (H5/A4) Control unit: The total current consumption (including the charging current at 24V) for the selected control unit (c.i.e.) when it is connected to the mains (230 V AC), i.e.
  • Page 127: Display Current Consumption On Com-Loop (H5/A5)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 27.5 Display current consumption on COM-loop (H5/A5) The current consumption (an average value) for each COM loop can be displayed. NOTE! No or very small current consumption (< 10 mA) cannot be presented correctly / precisely since the accuracy is ±5 mA.
  • Page 128: Display Statistics For Communication (H5/A6)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 27.6 Display statistics for communication (H5/A6) The statistics can be used during commissioning, service, etc. Number of pollings is the number of pollings / "questions" sent out by the control unit to all the units connected on the COM loop.
  • Page 129 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Number of pollings: nnnnnnn Info. automatically Parity fault: 000000 00.0% updated each 5 second. Number of bits fault: 000000 00.0% No answer: 000000 00.0% Bit length fault: 000000 00.0%...
  • Page 130: Activate Address Setting Mode For Du (H5/A7)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 27.7 Activate address setting mode for DU (H5/A7) This function can be used by commissioning / service engineer to activate the address setting mode in the following Display Units connected to the c.i.e.:...
  • Page 131: Setup Wireless Detectors (H5/A8)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 27.8 Setup wireless detectors (H5/A8) This function can be used by commissioning / service engineer to set a Base station for wireless units (4620) to one of the following modes:...
  • Page 132 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x E.g: Set base station mode If the specified Base √ "000001" Set base station 000001 to Register station doesn't exist, it will "Register" Unregister be indicated by "X"...
  • Page 133: Ssd Information (H5/A9)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 27.9 SSD information (H5/A9) SSD name As written in the EBLWin dialog box "System Properties" (Name). Downloaded Date and time when the SSD was downloaded.
  • Page 134: Fault Acknowledge (H6)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x FAULT Acknowledge (H6) Regarding fault indication, etc., see chapter "Fault", page 57. See also chapter "Fault acknowledge", page 77. All faults and the status / action are stored in the event log and can be listed, see chapter "Event log (H4/U7)", page 117.
  • Page 135 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x ↲ " " A corrected / serviced FAULT: Low battery capacity, control unit 00 fault that is acknow- yyyy-mm-dd hh:mm /Acknowledged ledged will disappear FAULT: No reply zone 045 address 06 from this list.
  • Page 136: Perform Zone Test (Test Mode) (H7)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Perform ZONE TEST (Test mode) (H7) Normally, zones are tested during the monthly test via menu H1. Via this menu (H7) it is also possible to perform the zone test. Up to 100 zones can be set in test mode.
  • Page 137 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Action Text in display Comments " " According to chapter Menu "Access", see page 88. Scroll to menu H7. H7 Perform ZONE TEST ↲...
  • Page 138 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x The zone(s) will stay in test mode until the test mode is ended. The test mode is ended in this menu or automatically one hour after the latest test alarm. Valid for each zone respectively.
  • Page 139: Maintenance (H8)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Maintenance (H8) 30.1 Password for service / maintenance Only authorised personnel have access to the level 3A menus (e.g. H8) and a password for level 3A (Service technician) is required.
  • Page 140 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Write COM loop number Disconnect The loop will directly be √ COM loop 0, control unit 00 and control unit number. shown in the Re-connect ↲...
  • Page 141: Acknowledge Service Signal (H8/S2)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 30.3 Acknowledge SERVICE signal (H8/S2) When SERVICE signal is generated in the system, following symbol is shown in the display's symbol area: See also chapter "Sensors activating SERVICE signal (H4/U5)", page 115.
  • Page 142 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x ↲ " " The acknowledged sensor Sensor, Zone XXX address AA needs service disappears from the list. technical address xxxxxx Continue like above or 2012-11-03 09:09:35 press "...
  • Page 143: Clear Weekly Average (H8/S3)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 30.4 Clear weekly average (H8/S3) Valid only for 430x, 4400 and 4401 sensors in NORMAL mode: If a sensor (analog smoke detector) is replaced without having generated SERVICE signal, its week average sensor value has to be cleared and set to the default value (i.e.
  • Page 144: Test Of Alarm Devices (H8/S4)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 30.5 Test of alarm devices (H8/S4) The programmable outputs of type "Alarm device" can be collectively activated via this menu (H8/S4), which makes it possible to test the alarm devices.
  • Page 145 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x ↲ " " Test of alarm devices, control unit 00 The test will continue for in progress. Press ↵ to end test one hour if not stopped via...
  • Page 146: Safe Shut Down Of Control Unit (H8/S5)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 30.6 Safe shut down of control unit (H8/S5) It's recommended to do a safe shut down of control unit before you power off a control unit (i.e. no 230 V AC and no battery). Safe shut down will save the SSW in a Flash ROM and put the CPUs at rest.
  • Page 147 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Power off / Power on After a restart (see page FAULT: Restart control unit 00, code 50 84), there will always be address 0 after 5 min.
  • Page 148: Activate Address In Alarm Mode (H8/S6)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 30.7 Activate address in alarm mode (H8/S6) One alarm point (zone-address), not a whole zone, can be set in alarm. It will be presented in this control unit as a fire alarm, the built-in LED in the alarm point (e.g.
  • Page 149 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x First alarm: 123-45 Alarm number 1(of 1) This manually activated fire alarm will be Test mode presented in all control Zone Address unit displays and all ext.
  • Page 150: Synchronize The Control Units (H8/S7)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 30.8 Synchronize the control units (H8/S7) After any control unit restart, synchronization will start automatically. Synchronization can also be started via EBLWin and via this menu (H8/S7).
  • Page 151 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x "▼" Synchronization in progress... During the synchronization ↲ " " the progress symbol for each control unit is shown. CU00 ↻ CU10 ↻ CU20 ↻...
  • Page 152: Activate / Reset Outputs (H8/S8)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 30.9 Activate / Reset outputs (H8/S8) Any output can be activated, i.e. the function can be tested. (Can also be done via EBLWin.) The selected output will be activated no matter if the control expression is true or not.
  • Page 153 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Change type output will directly be of output shown in the Reset list Write loop unit Activate If the specified output technical number and √...
  • Page 154: Interlocking Outputs And Inputs (H9)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Interlocking outputs and inputs (H9) 31.1 Activated interlocking outputs / inputs (H9/C1) Action Text in display Comments " " According to chapter Menu "Access", see page 88.
  • Page 155: Activate / Deactivate Interlocking Output (H9/C2)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 31.2 Activate / deactivate interlocking output (H9/C2) The output in each interlocking combination (area / point) can be manually activated via this menu. The corresponding interlocking input will be "monitored"...
  • Page 156 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x "|" -- Activate ---------------------------------------------------------- Select in the Deactivate "▼" Interlocking output area: _ _ _ point: _ _ list with (in this example there is only...
  • Page 157: Disable / Re-Enable Interlocking Output (H9/C3)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 31.3 Disable / re-enable interlocking output (H9/C3) Interlocking outputs (Type = Interlocking) can be individually disabled via this menu (and collectively via menu H2/B3).
  • Page 158 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x "|" -- Disable ----------------------------------------------------------- Select in the Re-enable "▼" Interlocking output area: _ _ _ point: _ _ list with (in this example there is only...
  • Page 159: Change Password (H10)

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x 31.4 Change password (H10) The password for the person (user name) logged on to the control unit, can be changed via menu H10 but should normally be changed via EBLWin, i.e.
  • Page 160: Annual Control

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Annual control The building occupier is highly recommended, once a year, to do some tests, beside the monthly tests. To avoid the Fault tx output(s) to be activated, they can be disabled via menu H2/B5 (or via an open door, se chapter "Open door", page 38.).
  • Page 161: How To Change Paper In The Printer

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x How to change paper in the printer When the paper roll is almost empty, a red line appears on one edge of the paper. Change the paper roll before it is completely empty! Always have a spare paper roll on site (paper width 58 mm).
  • Page 162: Replacing A Tlon Connection Board And/Or The Main Board

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Replacing a TLON connection board and/or the Main board By the TLON network programming, some unique data will be stored in a memory on the 5090 TLON connection board and some will be stored in a memory on the 5010 main board.
  • Page 163: Battery Maintenance

    Operating Instructions Fire alarm system EBL512 G3, V2.2.x Battery maintenance The batteries - 2 x 12 V, 28 Ah (e.g. Panasonic LC-P1228AP) - are placed inside the control unit. Larger batteries (< 65 Ah) have to be placed outside the control unit, e.g. in a separate battery cabinet, etc.
  • Page 164: How To Avoid Unnecessary (Nuisance) Fire Alarms

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x How to avoid unnecessary (nuisance) fire alarms We all realise, when life, buildings, production facilities, etc. shall be saved, it is of utmost importance that an initial fire is detected as soon as possible.
  • Page 165 Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Exhausts Exhausts from cars / trucks, lift trucks, lawn mowers, etc. influences smoke detectors (sensors). If windows and doors are open, exhausts can "slip in" that way.
  • Page 166: Information Regarding Radioactive Radiation Source164

    Operating Instructions Fire alarm system EBL512 G3, V2.2.x Information regarding radioactive radiation source Today, Panasonic have no ionization smoke point detectors but old detectors connected to the EBL512 G3 installation might be smoke sensors / detectors of the ionization type.
  • Page 167: Revision History

    Panasonic Eco Solutions Nordic AB MEW01777 Rev: - Operating Instructions Fire alarm system EBL512 G3, V2.2.x Revision history...
  • Page 168 This page has deliberately been left blank.
  • Page 169 Panasonic Eco Solutions Nordic AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 E-mail: info.pesn@eu.panasonic.com • Internet: http://pesn.panasonic.se...