Login, according to chapter "Access", page 88.
Use menu H6 (access level 2B) for fault acknowledge, see
chapter "FAULT Acknowledge (H6)", page 132. Menu H6
is a list showing a maximum of 300 faults (not acknow-
ledged faults and/or acknowledged but not serviced /
corrected faults).
All faults have to be individually acknowledged one by one
by the key pad button  . Use  or  to scroll.
If a fault has been corrected before it has been
acknowledged, the text
time. It still has to be acknowledged.
When a fault is corrected / serviced and acknowledged, it
will disappear from the list (H6).
When all faults have been acknowledged, output(s) for
routing equipment (Fault tx) is (are) reset (i.e. the LED
Routing equipment "Fault tx activated" (L13) will be
turned off).
As long as there are faults (i.e. not acknowledged faults
and/or acknowledged but not corrected faults) the LED
Fault / Disablements "General fault" (L9) will be lit and
general fault (and maybe general charge fault) output(s) are
activated.
Faults, corrected faults and acknowledged faults are shown
in the General event log (menu H4/U6).
32
In the Australian and New Zealand conventions the LED "L13" is turned
on and the output(s) for routing equipment (Fault tx) is (are) activated until
there are no faults in the system.
78
serviced
"
32
"
is added after the