Panasonic MEW01777 Operating Instructions Manual page 75

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
Ext. Fire Brigade Panel 1826 / 1828.
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: Supervised input x expansion board
x, control unit xx
A fault on the supervised input x on the expansion board 4583 with
address x, in control unit no. xx.
Check the cables / connections (cut-off or short-circuit).
FAULT: Supervised output x,
control unit xx
If the output is programmed for sounders (type "Alarm devices"), it is
also indicated by LED Fault / Disablements "Alarm devices" (L11)
blinking.
If the output is programmed for fire brigade tx (type "Routing
equipment"), it is also indicated by LED Fault / Disablements "Fire
brigade tx" (L12) blinking.
If the output is programmed for an extinguishing system (type
"Extinguishing"), there will be an additional information text close to
the soft key area in the display: Extinguishing wire fault
x=0 (S0): Short circuit/break on the connected cable/ equipment
and/or blown fuse F4 on the main board 5010.
x=1 (S1): Short circuit/break on the connected cable/ equipment
and/or blown fuse F5 on the main board 5010.
x=2 (S2): Short circuit/break on the connected cable/ equipment
and/or blown fuse F6 on the main board 5010.
x=3 (S3): Short circuit/break on the connected cable/ equipment
and/or blown fuse F7 on the main board 5010.
Fuse T500mA L 250V (TR5).
Calibration not performed via menu H5/A1.
Connected equipment might be "stolen".
Resistor(s) missing or not correct value. (1-5 resistors
33K)
NOTE! The calibrated value has to be in the range 1K-50K.
For EN54 compliance: The calibrated value has to be 1K.
FAULT: Supervised output x expansion board
x, control unit xx
A fault on the supervised output x on the expansion board 4583 with
address x, in control unit no. xx.
If the output is programmed for sounders (type Alarm devices), it is
also indicated by LED Fault / Disablements "Alarm devices" (L11)
73
.

Advertisement

Table of Contents
loading

Table of Contents