Panasonic MEW01777 Operating Instructions Manual page 62

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
The Aspiration smoke detector Aspect Lazeer is not working as it
should be, i.e. the unit has not been calibrated in conjunction with
commissioning.
FAULT: Aspect not calibrated zone xxx
address xx and zone xxx address xx
The Aspiration smoke detector Aspect Nitro / Grizzle is not working
as it should be, i.e. the unit has not been calibrated in conjunction with
commissioning.
FAULT: Aspect zone xxx address xx
Check the specified Aspiration smoke detector Aspect Lazeer. (One
detection area, one or two pipelines per detection area.)
FAULT: Aspect zone xxx address xx and zone
yyy address yy
Check the specified Aspiration smoke detector Aspect Nitro / Grizzle.
(Two detection areas, one or two pipelines per detection area.)
FAULT: Battery not connected,
control unit xx
Battery voltage is below 18.9 V.
Batteries (2 x 12 V) are missing or not connected
correctly.
Fuse F2 on the Main board 5010 is blown.
Other / external battery fuse is blown.
This check is done every 14
the check is done every 30
ceramic).
FAULT: Battery, technical number xxxxxx
The charging function in the external power supply 3366 connected on
the COM loop is not OK.
 Batteries (2 x 12 V) are missing or not connected correctly.
 The p.c.b. is faulty and has to be replaced.
FAULT: Battery zone xxx address xx,
technical number xxxxxx
60
th
minute but when the fault is generated
th
sec. Fuse: T6.3A H 250V (5x20 mm