Panasonic MEW01777 Operating Instructions Manual page 72

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
The unit (e.g. a customized unit), cannot be found by the control unit.
Check the unit's COM loop address (with the
programming tool 3314 / 4414).
Check the downloaded site specific data (SSD).
The unit might be faulty.
The unit might be removed from the COM loop.
There might be a double break or short-circuit on the
COM loop.
FAULT: No reply zone: xxx address: xx
technical number xxxxxx
The unit cannot be found by the control unit.
Check the unit's COM loop address (with the
programming tool 3314 / 4414).
Check the downloaded site specific data (SSD).
The unit might be faulty.
The detector might be removed from its base.
There might be a double break or short-circuit on the
COM loop.
Valid for a wireless smoke detector 4611: Battery
voltage < 2.3 V or the Base station (4620) do not receive
any detector data.
FAULT: No reply zone: xxx address: xx and
zone: yyy address: yy
technical number xxxxxx
The unit (Aspirating smoke detector Aspect Nitro / Grizzle), cannot be
found by the control unit.
Check the unit's COM loop address (with the
programming tool 3314 / 4414).
Check the downloaded site specific data (SSD).
The unit might be faulty.
The detector might be removed from its base.
There might be a double break or short-circuit on the
COM loop.
FAULT: Printer, control unit xx
This is valid for an EBL512 G3, type 5000 with printer. Control unit
no. xx.
Faulty printer
Printer not correctly connected.
No paper.
Printer selected in EBLWin but no printer mounted in the
70