16.5.1
First alarm: 000-00
16.5.2
Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Key cabinet alarm

The fire brigade uses a key cabinet to store a key to the building.
One programmable input per c.i.e. can be used to connect a key
cabinet.
A key cabinet alarm is like a normal fire alarm, i.e. outputs with
trigger condition "General fire alarm" will be activated as well as
outputs with trigger condition "Activated key cabinet"

Key cabinet opened before a fire alarm

If the key cabinet is opened before a fire alarm (e.g. if somebody
illegally breaks into the key cabinet), a key cabinet alarm will be
activated.
An example, XX = Control Unit number (00-29):
Alarm from key cabinet control unit XX
Menu
When printer is available the Key cabinet alarm will be printed like
for a normal fire alarm (see above).
Key cabinet alarm is reset like a normal fire alarm, see chapter "Fire
alarm reset, page 53.
This alarm will also generate a fault message, see chapter "Key
cabinet alarm reset", page 55. It is indicated by LED "General fault"
(L9) and the "Fault tx" output(s) will be activated.

Key cabinet opened in conjunction with a fire alarm

If a normal fire alarm already is activated in the c.i.e. the fire brigade
personnel can open the key cabinet without activating any key cabinet
alarm or fault.