MEW01777
27.4
Action
Text in display
"
"
Menu
Scroll to menu
H5 Service
H5.
"
"
A1 Calibration of supervised output
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in control unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
Scroll to menu
A4 Display current consumption in control unit
A4.
Select control unit: : 00 (press ↵)
"
"
"
"
Please wait......
No reply from control unit.....
Current consumption in control unit 00:
From rectifier: xxxx mA
Charging: xxxx mA (battery temperature xx°C)
Low capacity voltage diff: xxxxx mV
"
" or "
"
A4 Display current consumption in unit
ESC
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
Display current consumption in unit
(H5/A4)
Control unit: The total current consumption (including the charging
current at 24V) for the selected control unit (c.i.e.) when it is
connected to the mains (230 V AC), i.e. this function is not working
by battery backup.
Charging: The battery charging current for the selected control unit
(c.i.e.). Also battery temperature and "low capacity voltage" will be
53
shown.
53
During the battery capacity check the voltage is measured with and
without a resistor. A difference between these two voltages > 700 mV will
result in a "Low battery capacity" fault. Checked every 4
53
124
Comments
According to chapter
"Access", see page 88.
Write control unit number
and press "
".
If the control unit don't
exist or don't answer.
Info. automatically
th
updated each 5
second.
Scroll to another menu or
press "
".
ESC
th
hour.