Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Routing equipment (H2/B5)

Disabled outputs are listed in menu H4/U1 from which it is possible to
get a print-out.
Outputs for routing equipment (fire brigade tx and fault tx) can be
disabled and re-enabled via this menu. Can be useful during an
installation and test period, when only local alarms are required.
Disabled output for routing equipment is indicated by LEDs Fault /
Disablements "General disablements" (L10) and "Fire brigade tx"
(L12).
Disabled output will stay disabled until re-enabled again via this
menu.
Text in display
H2 Disable or re-enable
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
Escape
menu
B5 Routing equipment
Disable Routing equipment
Fire
Fault
104
Comments
According to chapter
"Access", see page 88.
Via menu B5 can the
standard outputs (fire
and fault) for routing
equipment be disabled.
"◄", "►"
Use
to
toggle between:
Fire
Fault
Press "
" to disable,
which will be indicated
with "√" and a beep.
The "type" will directly
be shown in the Re-
enable list