Panasonic MEW01777 Operating Instructions Manual page 21

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
Rev: -
Push button
P1
Silence buzzer (yellow)
P2
Silence Alarm devices
(red)
P3
Reset (green)
P4 – P7
Soft keys (grey)
P8
Alarms queued (grey)
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
Push buttons on the Fire Brigade Panel (FBP)
Operation/function
Used to silence the buzzer in the c.i.e. when it is sounding.
Used to silence alarm devices / sounders
when they are sounding. Silenced Alarm devices is indicated
to the right in the display's soft key area (a symbol near this
button), see page 22.
Used to reset:
Fire alarms (see below)
Co-incidence alarms (if not automatically reset)
For more information see "Alarm reset", page 53.
NOTE! P3 has to be pressed for > 0.5 sec.
The operation/function is shown above the key in the display
(i.e. the soft key area). The function of a soft key may vary
depending on the situation. If nothing is shown above the
key in the display, the key has no function for the moment.
Used when LEDs "Alarms queued" (L6) are lit, to
scroll/browse through the queued alarm points (zone–
address). Function, see chapter "Fire alarm", page 42, under
LEDs "Alarms queued".
NOTE! To scroll/browse through the queued zones, use the
soft key "Next zone" (P5).
NOTE! Fire alarms are:
Fire alarm
Heavy smoke/heat alarm
Alert Annunciation (AA) alarm
Key cabinet alarm
Encapsulated reset (aut. disablement):
approx. 0.1 sec. later also "Alarms queued" (P8). See also page 54.
Multiple reset (when Single reset is selected): Press "Reset" (P3) and
approx. 0.1 sec. later also ↵ ("Enter").
3
Outputs of type "Alarm devices" will be de-activated.
4
The soft key "P7" has the function Evacuate in the following conventions:
Belgian, British Standard, Hungarian, Spanish and Ukrainian. In all other
conventions it has the function Alert Annunciation Acknowledge.
19
3
in the building
Press "Reset" (P3) and
4

Advertisement