Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Clear weekly average (H8/S3)

Valid only for 430x, 4400 and 4401 sensors in NORMAL mode:
If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be
cleared and set to the default value (i.e. "1" = 0.1 %/m), otherwise the
new / clean sensor will inherit the old sensor's value. It is possible to
clear the week average sensor value for each sensor individually via
this menu.
NOTE! First replace the sensor and then clear the week average
value as soon as possible. Authorised service personnel only, must
do this. Used incorrectly it can cause nuisance fire alarms.
The first week average sensor value (after clearing) will be calculated
within one hour, then each week.
Text in display
H8 Maintenance
S1 Dis- / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of control unit
S6 Activate address in alarm mode
S7 Synchronize the control units
S8 Activate / Reset outputs
S3 Clear weekly average
Clear weekly average zone: 000 address: 00
(press ↵)
Weekly average zone 001 address 01 cleared
S3 Clear weekly average
141
Comments
According to chapter
"Access", see page 88.
Write the wanted zone and
"↲ "
address and press
.
Continue like above or
scroll to another menu or
press "
".
ESC