  • Page 1 4479 ADDRESSABLE SOUNDER BASE Fire alarm solutions technical description www.panasonic-fire-security.com...
  • Page 2: Table Of Contents

    Table of Contents INTRODUCTION ABBREVIATIONS GENERAL DESCRIPTION 3.1. SOUNDER 3.2. BASE PROGRAMMABLE SOUNDER 4.1. PRIORITY LEVELS 4.2. NORMAL SPL 4.3. LOW POWER SPL 4.4. TONES SET THE COM LOOP ADDRESS 5.1. AUTO ADDRESSING 5.2. MANUAL ADDRESSING SET THE MODE 6.1. COMPATIBILITY TABLE MOUNTING 7.1.
  • Page 3: Introduction

    4479 ADDRESSABLE SOUNDER BASE - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 1. INTRODUCTION This document describes the Addressable sounder base, type number 4479. The document contains information about the product and instructions on how to mount and connect it.
  • Page 4: Abbreviations

    2. ABBREVIATIONS Decibel Sound Pressure Level [dBA @1m]...
  • Page 5: General Description

    4479 ADDRESSABLE SOUNDER BASE - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 3. GENERAL DESCRIPTION The addressable sounder base is intended for indoor use and in dry premises. The sounder base is mounted in the ceiling and the analog multi detector with isolator 4400I must be plugged in the base. The base is connected to the COM loop.
  • Page 6: Sounder

    3.1. SOUNDER The sounder has seven different tones. These tones can be used in the three priority levels; high, medium, and low. 3.2. BASE Ceiling mounted. Cannot be used without a detector. The short circuit isolator is in the detector, so without detector 4400I you will have an open circuit.
  • Page 7: Tones

    4479 ADDRESSABLE SOUNDER BASE - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 4.4. TONES The sounder has seven selectable tones. This configuration is done in EBLWin. The values in the tables below are minimum sound pressure level. TONE 1 Continuous Horizontal orientation L[dB]...
  • Page 8 TONE 5 Dutch Fire Intermittent Horizontal orientation L[dB] Vertical orientation L[dB] Sweep (NEN 2575) 500Hz to 1200Hz 15˚ 45˚ 75˚ 105˚ 135˚ 165˚ 15˚ 45˚ 75˚ 105˚ 135˚ 165˚ 3s sweep, 0.5s silence 81.0 86.3 87.3 85.5 77.7 81.2 84.5 80.7 87.1 87.1...
  • Page 9 4479 ADDRESSABLE SOUNDER BASE - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION Vertical orientation Horizontal orientation...
  • Page 10: Set The Com Loop Address

    AUTO ADDRESSING The sounder base 4479 with detector 4400I supports automatic addressing via the EBLWin. The sounder base 4479 has no short circuit isolator, which is necessary for automatic addressing. But in conjunction with 4400I, auto addressing is possible. To be able to auto-addressing a unit, the unit must have its default address.
  • Page 11: Set The Mode

    4479 ADDRESSABLE SOUNDER BASE - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 6. SET THE MODE The 4479 is set to advanced mode by default. 6.1. COMPATIBILITY TABLE Advanced mode NORMAL mode 2330 mode 2312 mode EBLOne V ≥ 3.3 Not used...
  • Page 12: Mounting

    7. MOUNTING The addressable sounder base must be mounted in the ceiling. Screws are not supplied. (Measure in mm) The addressable sounder base cannot be used without a detector. The short circuit isolator is in the detec- tor, so without detector 4400I you will have an open circuit. If the addressable sounder base is mounted on an impenetrable ceiling, for example concrete ceiling, and with the cabling entering from the sides of the product, there is no need for any ingress protection.
  • Page 13 4479 ADDRESSABLE SOUNDER BASE - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 7.1. MOUNTING WITH INGRESS PROTECTION FOR SOUNDER BASE If the sounder base is mounted with the cabling entering from above (through the inner ceiling), there is a need for an ingress pro- tection (type 4489) to maintain IP 21 of the sounder base.
  • Page 14: Lock Screw

    7.2. LOCK SCREW The sounder base 4479 is prepared for mechanical locking with detector 4400I. a) Drill the lock screw hole (2.5-2.7 mm) through the detector. b) Place the detector in the base with the detector's "Mark" in the same position as the "Mark" on the base and turn the detector clockwise.
  • Page 15: Installation And Wiring

    B direction The base is prepared for mechanical locking of the detector when a detector with a locking screw is plugged into the base. Analog detector with isolator 4400I must be plugged in the addressable sounder base 4479. Terminal name...
  • Page 16: Technical Data

    Maximum 95 % RH (Non condensing) Ingress protection rating IP21 C Size: H x W x D 160 x 102 x 25.4 mm Weight 102.5 g 4479 White (10Y9/0.5, Munsell colour code) Colour 4479-B Matte Black (N1.5 Munsell colour code)
  • Page 17: Approvals

    4479 ADDRESSABLE SOUNDER BASE - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION 10. APPROVALS Applicable directive/ Approval Applicable standards Notified body EN 54-3: 2001+A1:2002+A2:2006 No. 0786-CPR-21564 EN54-3 VdS 2344 No. G218002 VdS 2543 EN61000-6-3 (Emission) Self declaration EN50130-4 (Immunity) RoHS EN IEC 63000...
  • Page 18 DOCUMENT NAME: TECHNICAL DESCRIPTION 4479 DOCUMENT NUMBER: MEW02073 EN DATE OF ISSUE: 2018-01-30 REV: 4 DATE OF REVISION: 2023-06-15 Panasonic Fire & Security Europe AB Jungmansgatan 12 SE-211 11 Malmö Tel: +46 (0)40 697 70 00 www.panasonic-fire-security.com...