Check the type of unit, which should be the same as programmed via
EBLWin.
FAULT: Wrong type of unit zone: xxx
address: xx and zone: yyy address: yy
technical number xxxxxx
Check the type of unit (Aspirating smoke detector Aspect Nitro /
Grizzle), which should be the same as programmed via EBLWin.
FAULT: Zone line input, Zone xxx Address xx
CU xx expansion board x input x
Valid for the 8 zones exp. board 4580 zone line input x (xxx-xx =
zone – address). The board is mounted in control unit xx.
Break on the zone line, wrong / no end-of-line device / short-circuit (if
not programmed for fire alarm at short-circuit).
FAULT: Zone line input, zone: xxx address:
xx technical number xxxxxx
Valid for the Multipurpose I/O unit 3361 monitored zone line input Z.
Break on the zone line or wrong / no end-of-line capacitor (10 μF) or
short-circuit (if not programmed for fire alarm at short-circuit).
No contact with main board
Shown only in the affected control unit.
 Check that "MMI board" is selected in the SSD (EBLWin,
Control unit properties).
 Fault in the Main board 5010 software or hardware. Check the
cable between the Main board and MMI board. This is a very
serious
fault.
immediately.
 In conjunction with SSD download: Erase the SSD in the
control unit and download the SSD again.
(External fault; User programmable text)
Programmable input is connected to any external equipment's fault
output. User definable fault message (< 40 characters) has to be
programmed via EBLWin. Note, The prefix "FAULT:" will not be
automatically added.
76
Call
for
service
personnel/engineer