Test Of Alarm Devices (H8/S4) - Panasonic MEW01777 Operating Instructions Manual

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
30.5
Action
"
"
Menu
Scroll to menu H8.
"
"
Scroll to menu S4.
"
"
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Test of alarm devices (H8/S4)

The programmable outputs of type "Alarm device"
collectively activated via this menu (H8/S4), which makes it possible
to test the alarm devices.
The test cannot be started if a fire alarm already is activated in the
system.
One or all control units can be selected. When the test starts, the
alarm devices will sound continuously (steady)
seconds, be silent for approx. 25 seconds, sound for approx. 5 seconds
and so on.
NOTE! Disabled (and silenced) alarm devices will also be tested.
The test will continue for one hour if not stopped via this menu
(H8/S4) or if a fire alarm is activated in the system.
Text in display
H8 Maintenance
S1 Dis- / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of control unit
S6 Activate address in alarm mode
S7 Synchronize the control units
S8 Activate / Reset outputs
S4 Test of alarm devices
Test of alarm devices control unit: 00
Press ↵ to start test.
56
Including Addressable siren 3377 / 4477 and Addressable sounder base
3379.
57
For the alarm devices 3377 / 4477 and 3379 the tone with the highest
priority level (and type "alarm device") will be automatically selected.
All
142
56
can be
57
for approx. 5
Comments
According to chapter
"Access", see page 88.
Write control unit number
or press "►" for "All".
Press "
" to start the test.