Operating Instructions Fire alarm system EBL512 G3, V2.2.x
The delay time (0-255 sec.) is, for the whole system, set via EBLWin
(System Properties, page 1). The delay time will be added at the end
of the alarm algorithm when a fire alarm normally would have been
activated. For that reason this "extra" delay time should be as short as
possible.
The Delayed alarm will be activated when the delay time countdown
has started and will be activated until the delay time has run out and a
normal fire alarm is activated. No outputs will be activated.
In case of a Delayed alarm, the following happens:
 The buzzer in the c.i.e. sounds 0.8 sec. each 5
sec.).
 In the c.i.e. display, a presentation number (zone/address) is
shown (for the first delayed alarm). Also a user definable
text message (= the alarm text for fire alarm) is shown (if
programmed).
Example; Delayed alarm zone 123, address 45 (within zone 123):
Delayed alarm
Zone
123-45
User definable alarm text for 123-45.
Menu
"
" after the presentation number is automatically added
SMOKE
depending on the type of alarm point (i.e. SMOKE, HEAT, MULTI or
MCP).
NOTE! The text "
Menu
display, only if the door in the CU is open.
If more than one Delayed alarm is activated, the LEDs "Alarms
queued" (L6) are blinking and the Delayed alarms will be
automatically scrolled (each 5
Delayed alarms are automatically reset see chapter "Alarm reset",
page 53.
50
Address
" for the soft key "P4" is visible in the
th
second).
th
sec. (0.8 / 5
SMOKE