Activate / Reset Outputs (H8/S8) - Panasonic MEW01777 Operating Instructions Manual

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
30.9
Action
"
"
Menu
Scroll to menu H8.
"
"
Scroll to menu S8.
"
"
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Activate / Reset outputs (H8/S8)

59
Any output
can be activated, i.e. the function can be tested. (Can
also be done via EBLWin.)
The selected output will be activated no matter if the control
expression is true or not.
The selected output will be reset only if the control expression is false
(not true). If the control expression is true when you reset the output
via menu H8/S8, the output will remain activated until the control
expression is false (not true) again.
Text in display
H8 Maintenance
S1 Dis- / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of control unit
S6 Activate address in alarm mode
S7 Synchronize the control units
S8 Activate / Reset outputs
S8 Activate / Reset output
Activate
Loop unit 000000 output 0
59
Including Addressable siren 3377 / 4477 and Addressable sounder base
3379.
150
Comments
According to chapter
"Access", see page 88.
Via menu S8 can loop unit
output, control unit output
and expansion board
output be activated and
reset.
Use the soft key "
Change
" to toggle
type of output
between:
Loop unit output
Control unit output (S0-
S3 and R0-R1)
Exp. board output
Write loop unit technical
number and output number
and press "
" to activate,
which will be indicated
with "√" and a beep. The