    EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL 1. INTRODUCTION This document is intended to be used for the daily duties like disablements / re-enablement’s, zone tests, and so on in the EBL512 G3 system. Due to continual development and improvement different S/W versions can be found.
  • Page 4: Description Of The Front

    2. DESCRIPTION OF THE FRONT Menu Next zone Re-enable Evacuate 11 12 13 14...
  • Page 5: Led Indicators

    EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL 2.1. LED INDICATORS See reference picture on page 4. Fire Fire alarms Extinguishing Output(s) for extinguishing equipment activated Ventilation Output(s) for fire/smoke ventilation equipment activated Fire brigade tx Output "Fire alarm" for fire brigade tx (routing equipment) activated Steady light: c.i.e.
  • Page 6: Push Buttons

    2.2. PUSH BUTTONS See reference picture on page 4. Used to clear / delete all visible entry fields. Used to stop input of data or to step upwards in the menu system. Key pad Numeric key pad for the digits 0-9. Enter Used to accept / select a menu or input of data.
  • Page 7: Access Levels

    EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL 3. ACCESS LEVELS Level “Building officer” is described in this document. INFORMATION ONLY BUILDING OFFICER SERVICE PERSONNEL H4 Present system status H1 Perform monthly test H1 Perform monthly test H6 Display faults...
  • Page 8: Log On To The Control Unit (C.i.e.)

    4. LOG ON TO THE CONTROL UNIT (C.I.E.) USER NAME Up to ten users, 0 to 9, may be programmed. By default at delivery, three users are available: • 0 = Information only • 1 = Building officer • 2 = Service personnel PASSWORD Each User has a Password for an access level, for example.
  • Page 9: Navigation / General Procedures

    EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL 5. NAVIGATION / GENERAL PROCEDURES • Scroll in lists or menus with • Press to toggle between different choices. • Press soft key to toggle between different functions. • Press to select / accept.
  • Page 10: Perform Monthly Test (H1)

    6. PERFORM MONTHLY TEST (H1) a) Log on to the c.i.e. b) Menu H1 is selected. Press c) Press . The c.i.e. buzzer sounds, all the dots in the display are shown and all LEDs on the front are turned on. If the c.i.e.
  • Page 11: Sub Menu List (B1 - B6)

    EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL 7.1. SUB MENU LIST (B1 – B6) Disable Change type of disablement Press the Soft key to toggle between: - Zone 000 - Zone 000 address 00. Zone or Zone / Address If "Automatically re-enablement"...
  • Page 12: Set Calender And Clock (H3)

    8. SET CALENDER AND CLOCK (H3) a) Log on to the c.i.e. b) Navigate to menu H3. c) Press . Depending on if it is the date, time and/or the day that shall be set, press to highlight it. d) Use the keypad to enter new values. Press To exit the menu without making any changes, press ESC.
  • Page 13: Fault Acknowledge (H6)

    EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL 10. FAULT ACKNOWLEDGE (H6) LED "Fault tx activated" on the front is indicating that the output for Fault condition routing equipment is activated. The LED will be turned off when all faults are acknowledged.
  • Page 14: Perform Zone Test (H7)

    11. PERFORM ZONE TEST (H7) Up to 100 zones can be set in test mode, which is indicated by the LED "Test mode" on the front. After one hour without any testing activity, the test mode will be automatically ended. Valid for each zone respectively. When an alarm point in a zone, set in test mode, is tested, it is presented in the display as a fire alarm, but with the information "Test mode"...
  • Page 15: Interlocking Outputs And Inputs (H9)

    EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL 12. INTERLOCKING OUTPUTS AND INPUTS (H9) a) Log on to the c.i.e. b) Navigate to menu H9. c) Press . A sub menu list (C1 – C3) will be displayed. 12.1.
  • Page 16 This product has been tested and approved to the highest standards, ensuring high quality and reliable fire alarm solutions. Panasonic Fire & Security Europe AB Jungmansgatan 12 SE-211 11 Malmö, Sweden +46 (0) 40 697 7000 www.panasonic-fire-security.com EN54 Daily user's manual: MEW02761 EN rev -...