Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Output type (H2/B3)

All outputs of type "Control", "Ventilation", "Extinguishing" and
Interlocking can be collectively disabled. Disabled output will stay in
(or return to) the normal condition for the output respectively.
Disabled outputs are listed in menu H4/U1 from which it is also
possible to get a print-out.
Text in display
H2 Disable or re-enable
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
Escape
menu
B3 Output type
Disable output type
Control outputs in Control unit 00
All
Change type of
disablements
100
Comments
According to chapter
"Access", see page 88.
Via menu B3 can
outputs of the same type
be collectively disabled
in selected control unit
or all.
Use the soft key "
Change
" to
type of disablements
toggle between:
Control
Ventilation
Extinguishing
Interlocking
Write control unit
number when required.
Press "
" to disable,
which will be indicated
with "√" and a beep.
The "type" will directly
be shown in the Re-
enable list