User Level, User Name & Password - Panasonic MEW01777 Operating Instructions Manual

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
Rev: -
7
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
User level, User name & Password
EBL512 G3 has different user levels for different kind of users.
To log on to an EBL512 G3 (version > 2.0) a User name and a
Password are required. Ten different User names with individual
Passwords can be used. Each User name is for a specific user level,
which has access to specific menus according to the following table.
User level
User level name /
according
type
to EN54-2
1
-
2A
-
2B
Information only
2C
Building officer
3A
Service personnel
3B
-
4
-
a)
Information only, i.e. the faults cannot be acknowledged.
b)
Menu H9/C1 only.
Via EBLWin (menu "System") ten different User names with
individual Passwords are possible to define in the "User data" dialog
box. One of three different levels /Types can be selected for each user
name. They have to be used to log on to an EBL512 G3 (version >
2.0) and/or for Web-server access. Three User names and Passwords
are default:
26
Required action /
equipment
No. (Hole in the
Plexiglas.)
Fire brigade key. (To
open the door.)
Like 2A + log on as
"Information only"
Like 2A + log on as
"Building officer"
Like 2A + log on as
"Service personnel"
PC + EBLWin + H/W
key (EBLWin key)
PC + EBLWin + H/W
key (EBLWin key) + a
special password
Access to
Alarms queued
button.
Like 1 + Silence
buzzer, Silence
alarm devices &
Reset buttons.
Like 2A + keypad.
a)
Menu H4, H6
,
b)
H9
& H10
Like 2A + keypad.
H1-H4, H6, H7,
H9 & H10
Like 2A + keypad.
H1-H10
SSD & S/W
download
SSD & S/W
download + reset
of alarm counter.

Advertisement

Table of Contents
loading

Table of Contents