blinking.
If the output is programmed for fire brigade tx (type Routing
equipment), it is also indicated by LED Fault / Disablements "Fire
brigade tx" (L12) blinking.
Calibration not performed via menu H5/A1.
Short-circuit / break on the connected cable / equipment.
Blown fuse F1 (Output 0) or F2 (Output 1) on the 4583
board. Fuse T200mA L 250V (TR5).
Connected equipment might be "missing".
End-of-line resistor(s) missing or not correct value, 1-5
resistors (33K).
NOTE! The calibrated value has to be in the range 1K-50K.
For 4583DE: Outputs 0 and 1 the termination resistor value shall be
200 – 1000 ohm.
FAULT: Supervised output x,
technical number xxxxxx
This fault message is valid for a COM loop output unit 3364 output.
If the output is programmed for sounders (type Alarm devices), it is
also indicated by LED Fault / Disablements "Alarm devices" (L11)
blinking.
If the output is programmed for fire brigade tx (type Routing
equipment), it is also indicated by LED Fault / Disablements "Fire
brigade tx" (L12) blinking.
Calibration not performed via menu H5/A1.
Short-circuit / break on the connected cable / equipment.
Connected equipment might be "stolen".
End-of-line capacitor(s) missing or not correct value, 1-5
capacitors (470 nF).
NOTE! The calibrated value has to be in the range 470 nF – 5 x
470 nF (2350 nF).
FAULT: Temperature sensor, control unit xx
The sensor is not correctly connected or is missing.
FAULT: TLON-board (Network 0),
control unit xx
FAULT: TLON-board (Network 1),
control unit xx