Restart - Panasonic MEW01777 Operating Instructions Manual

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
Rev: -
21
Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Restart

A restart will delete or not delete the data in EBL512 G3. Below
follows an explanation of the different data, abbreviations and a table
showing how the data respectively is affected (cold or warm restart).
FF = Fire alarms and Faults.
D = Disablements
FFD = Fire alarms, Faults and Disablements.
SSW = Sensor min. / max. values & performance factor, passwords
supervised output calibration values and event logs.
WASV = Week Average Sensor Values
SSD = Site Specific Data, i.e. all the installation programming created
and downloaded via EBLWin.
S/W = Software, i.e. the EBL512 G3 system program.
Safe shut down of control unit (menu H8/S6) will save the SSW
data (i.e. not the week average sensor values) in a Flash ROM before
you power off (de-energize) EBL512 G3. Before the first "Safe shut
down" this memory is empty. After each "Safe shut down" the latest
SSW data is saved. When EBL512 G3 is powered up, the RAM will,
after the restart, read the SSW data saved in the Flash ROM.
The date & time and alarm counter value is stored in the memory of
the real time clock, i.e. the value will be retained also after the c.i.e.
has been de-energized.
NOTE! After any restart, a new week average sensor value will be
calculated within two minutes, for all the analog smoke detectors.
During these two minutes all fire alarms from analog smoke detectors
will be suppressed. Thereafter a new average sensor value will be
calculated each week.
Here follows a table describing the different reset alternatives and how
the data respectively is affected:
37
Changed via menu H10.
84
37
,