The zone(s) will stay in test mode until the test mode is ended. The test mode is ended in this menu or
automatically one hour after the latest test alarm. Valid for each zone respectively.
You will be automatically logged out 15 minutes after the latest "action" (using of any key) but the zone(s)
will stay in test mode until the test mode is ended, see above.
Perform the test as quickly as possible, since the output(s) for routing equipment (fire brigade tx) are disabled
(also the parts of the zones in test mode, not visible for the test personnel, are disabled).
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled",
i.e. fire alarm will be detected faster than normally.
In the tested alarm point, the LED will light up approx. 10 seconds and then the alarm point will be
automatically reset. There will be a test mode alarm indication in the c.i.e. display. The printer, if available,
will print out every tested alarm point (Zone: xxx Address: xx Time: HH.MM).
A detector in test mode is not able to generate a fault.
After 15 minutes
or
"
" and
ESC
"
"
Escape menu
"
"
Menu
Log in (see above),
select menu H1,
step down to this view.
"
"
Some national regulations also require a routine test of the routing equipment.
Press press "
" (i.e. select "No") for no test. If so, the monthly test is completed (see below).
or
Press "▼" and "
" (i.e. select "Yes") to start such a test. If so, the following will happen in the system:
 The c.i.e. "Fault tx" output will be de-activated (note that this output is activated in normal state),
indicated by the LED "Fault tx activated" (L13).
60 seconds count-down starts.
 After 30 seconds, also the c.i.e. "Fire brigade tx" output (and corresponding programmable outputs
type "routing equipment") will be activated, indicated by the LED "Fire brigade tx" (L3).
 After another 30 seconds, the test will be ended and the outputs and LEDs will return to "normal".
"▼" and "
"
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
Zones in test mode:
End test: 
001 002 003 004
Zone 001 in test mode
Zone 002 in test mode
Zone 003 in test mode
Zone 004 in test mode
(
NOTE! See chapter "The information area priority
order", page 24 regarding priority order.)
Zones in test mode:
End test: 
001 002 003 004
Please wait....
Test of routing equipment?
Test of routing equipment in progress.
nnn seconds left.
No
Yes
92
LED "Test mode" (L8)
will light up. Perform the
tests.
You are logged out but the
zone(s) are still in test
mode.
Press "
" to end test.
The LED "Test mode" is
turned OFF.
"nn" starts at 060 and will
count down to 000.