Operating Instructions Fire alarm system EBL512 G3, V2.2.x

The symbol area

The symbol area is at the top of the display, see chapter 6.1.
The following table explains the meaning of each symbol:
The symbol area
Indicating
The door is open in any c.i.e. or external FBP in the system. See
also page 38. See also menu H4/U3.
Loss of mains in any c.i.e. or ext. power supply unit in the system,
i.e. the unit respectively is out of 230 V AC and is power supplied
via batteries.
Service signal. The week average sensor value is over the service
level for one or more analog smoke detectors in the system. See
also page 115 and menu H4/U5. For the Multi detector with CO
(4402) it is also indicating that the CO sensor is > 60 months old.
The c.i.e. is set in "Sensitive fault detection mode" via menu
H5/A2, see page 121.
One or more "Technical warnings" are generated in the system. See
also menu H4/U6.
Note that the symbol area may be suppressed see 6.3.
23