Operating Instructions Fire alarm system EBL512 G3, V2.2.x
Text in display
H7 Perform ZONE TEST
Set in test mode
Zone 000
Set in test mode
Zone 001
-- End test mode ---------------------------------------------
Zone 001
-- Set in test mode --------------------------------------------
Zone _ _ _
End test mode
Zone 001
135
Comments
According to chapter
"Access", see page 88.
Press "
" to start the test
mode. Indicated by "√"
and a beep. If the
specified zone doesn't
exist, it will be indicated
with "X" instead of "√"
and a beep.
All zones set in test mode
will be shown in the "End
test mode" list.
Use the soft key "|" to
toggle between Set in test
mode and End test mode
list.
After the testing, select a
zone in the "End test
mode" list and press "
The test mode has to be
ended for all zones.
".